en_BA_RR30_IO-Link_V0.23.docx
18/40
Baumer Electric AG
13.01.2021/
Frauenfeld, Switzerland
-
To avoid false pulses due to short losses of a proper signal.
-
To straighten the clock / pace
Figure 21
Minimum Pulse Duration
Parameter name
Short Description
Rights
Unit / Allowed
values
Minimal Pulse
Duration.SSC1 Time
Sets / indicates the minimal pulse length
in milliseconds for the respective
switching signal channel (SSC).
rw
0 to 60000 ms
Default: 0 ms
Minimal Pulse
Duration.SSC1 Mode
0: Both Pulses: positive and negative
pulses are prolonged; 1: Positive Pulse:
only positive pulses are prolonged; 2:
Negative Pulse: only negative pulses are
prolonged
rw
- Both Pulses (Default)
- Positive Pulse
- Negative Pulse
4.3.8
Counter / SSC4
For each individual SSC a switching counter is implemented, which can be used as diagnosis data or also as
measurement value. The number of counts of each channel can also be mapped to the measurement data
channel MDC by adjusting the MDC source (See section 0).
Trigger of counter is on positive slope of related SSC.
By configuring SSC4, it is also possible to set up a binary signal related to the number of switch counts of
SSC1 or SSC2. An auto-reset and time filters are included, to be able to create a full-featured counter being
able to count lot sizes without any need to code software on the PLC.
As all SSCs, SSC4 can also be mapped to the digital output giving the possibility to create a stand-alone lot-
size counter.