Page 78
Note:
A “manual release” can still be initiated in “auto mode” but the LCS “Inhibit” control
WILL
NOT
inhibit / abort the agent release sequence.
Single Zone Activation,
the following discharge sequence is executed;
➢
Automatic Activation LED is illuminated on the Agent Release Module and Local Control
Station.
➢
Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign illuminated, aural alarm
sounds).
➢
Stage 2 outputs are switched to +24VDC. (FIRE ALARM, EVACUATE & DO NOT
ENTER signs illuminated, aural alarm sounds).
➢
Optional pre-release delay is started (Selected via FACP on-site programming).
➢
The delay times out and if the Interlock signal is ON, the selected circuit will activate.
➢
The Pressure Switch field input on the Termination Board is activated and the Agent
Discharge LED on the Agent Release Module and Local Control Station will be
illuminated.
➢
Activate gas-fired output.
Dual Zone Activation,
if the first zone goes into alarm the following steps are initiated;
➢
The automatic activation LED on the Agent Release Module and Local Control Station will
flash.
➢
Stage 1 outputs are switch to
–24VDC. [FIRE ALARM sign illuminated, aural alarm
sounds].
When the second zone goes into alarm, then the following steps occur;
➢
Automatic activation LED goes steady.
➢
Stage 1 outputs are switched to +24VDC. (FIRE ALARM & EVACUATE signs illuminated,
aural alarm sounds)
➢
Stage 2 outputs are switched to +24VDC. (DO NOT ENTER sign illuminated)
➢
Optional pre-release delay commences (Selected via FACP on-site programming).
➢
The delay times out and if the Interlock signal is on the selected circuit will activate.
➢
The Pressure Switch field input on the Termination Board is activated and the Agent
discharge LED on the Agent Release Module and Local Control Station will be
illuminated.
➢
Activate gas-fired relay output.
Service Switch
The service switch is situated on the Agent Release Module when activated causes the following;
➢
Electrically isolates the activation circuitry from the agent release device.
➢
Operates the System Inoperative output.
Note:
The service switch is
NOT
overridden by a manual discharge.
Lock-Off Valve
When the manual lock-off valve is operated;
➢
The agent is blocked from reaching the release valve.
➢
The lock-
off valve inhibit indicator LED’s on the Agent Release Module and Local Control
Station are illuminated.
➢
The system inoperative output operates.
Fault Monitoring
Fault conditions are initiated by:
➢
The Pressure Switch monitoring circuit.
➢
The Low Pressure Switch monitoring circuit.
➢
The Lock-off Valve monitoring circuit.
➢
Activation circuitry.
➢
Stage 1 outputs. (Aural & visual discharge alarms).
➢
Stage 2 outputs. (Aural & visual discharge alarms).
➢
A Zone Fault.
➢
A Fault on the interlock input.
➢
A Fault with a LCS.