Page 64
12.9
8 Way Relay Board
The Relay Board (BRD25EWRB) provides 8 programmable relays with 30VDC 1 Amp voltage free
change over contacts for control or monitoring purposes and comes fitted for internal or external FACP
use.
The functionality and programming of the relays is similar to the relays on the main board of the FACP.
By default the relays default to Common Alarm functionality.
All terminal points are protected.
The board switches the relays as determined by the panel. The relays can be controlled by:
➢
Zones Alarm
➢
Group Alarm
➢
Device Alarm
➢
Internal Output
➢
Panel Output
➢
Loop Output
➢
Panel Input
➢
Loop Input
➢
Reset
– relay is activated for 3 seconds when reset depressed
12.9.1
Internal Relay Board
Fit EOL Termination
Link 1 if Last Module
on Comms Bus
Address SW
(See Note)
Not used optional 27VDC
RS485 Control / 27VDC
Comms In
CN2
CN1
CN3
CN4
ON
+
-
TB8
TB7
TB6
TB5
TB4
TB3
TB2
TB1
SW1
O/P 8
N/C
COM
N/0
O/P 7
N/C
COM
N/0
O/P 6
N/C
COM
N/0
O/P 5
N/C
COM
N/0
O/P 4
N/C
COM
N/0
O/P 3
N/C
COM
N/0
O/P 2
N/C
COM
N/0
O/P 1
N/C
COM
N/0
1 2 3 4
O N
TB8
TB7
TB6
TB5
TB4
TB3
TB2
TB1
O/P 8
N/C
COM
N/0
O/P 7
N/C
COM
N/0
O/P 6
N/C
COM
N/0
O/P 5
N/C
COM
N/0
O/P 4
N/C
COM
N/0
O/P 3
N/C
COM
N/0
O/P 2
N/C
COM
N/0
O/P 1
N/C
COM
N/0
N/0 = Normally Open
COM = Common
N/C = Normally Closed
RS485 Control / 27VDC
Comms Out
Figure 90: Internal 8 Way Relay Board Front View showing connectors and Address Switch
Relay Connections
Terminal/s
Function
TB1 to 8
N/O = Normally Open,
C = Common
N/C = Normally Closed
Relay 1 to 8
Note: See Section 17 for Addressing Details (SW1)