Page 117
24.1
Procedure
The following tests are the minimum that shall be performed when commissioning a system using the
FireFinder PLUS
Fire Alarm Control Panel. Supplements to these tests may be added by way of
attachments or notation (
using waterproof ink
) to this documentation. If supplements or tests are
added reference to them shall be made at an appropriate point on this document.
This Commissioning Record provides a complete description of the installed system and its tested
performance at the time of being commissioned and should be completed in conjunction with the -.
➢
installer's statement(s); including 'as-installed' drawings; and
➢
detector test records,
24.2
System Information
Check relevant box
GENERAL
YES
NO
NA
(a) Equipment:
Equipment has been designed and constructed in
accordance with the relevant Standards.
(b) Installation:
Equipment has been located, installed and
interconnected in accordance with the system documentation
(c) Compatibility:
All detectors and other devices used in the system are
—
(i) listed in the operator’s manual;
(ii) compatible with the relevant parts of CIE, particularly that the
permitted number of detectors and other devices for each circuit is
not exceeded;
(iii) installed in an environment for which they are suitable;
(iv) not set to a sensitivity outside that prescribed in the relevant
product Standard.
(d) Alarm zone limitations:
The alarm zone limitations in Clause 2.4
of AS 1670.1 are not exceeded.
(e) Primary power source:
(i) The primary power source for the system has been provided in
accordance with AS/NZS 3000.
(ii) The isolating switch disconnects all active conductors.
(iii) Five operations of the primary power source switch did not cause
an alarm to be indicated on the system.
(f) Secondary power source:
(i) The secondary power source is of a suitable type and capacity
complying with the requirements of Clause 3.16.2 of AS 1670.1.
(ii) The float voltage, charger type and setting is correct and in
accordance with the battery manufacturer’s recommendation.
(g) Battery temperature and voltage:
The battery voltage
corresponds to that specified by the battery manufacturer for the
temperature measured after 24 hour quiescent operation.
(h) Alarm zone parameters:
Each alarm zone circuit is within the
equipment manufacturer’s specifications.
(i) Wire-free alarm zones:
Wire-free actuating device parameters
meet the minimum parameters specified by the manufacturer,