Page 60
12.5
16 Zone and 32 Zone Indicator Modules
This module (BRD43ZAMC) has 32 bi-
coloured LED’s which can be used to display the status of up to
32 individual Zones or 16 Zones with dual LEDs.
The zone numbers assigned to each LED are configurable and the LED’s will operate in the following
manner for the respective zone statuses:
ZONE STATUS
LED STATE
LED COLOUR
FIRE
ON STEADY
RED
DEPENDENCY B
FLASH
RED
DISABLED
ON STEADY
YELLOW
FAULT
FLASH
YELLOW
ALL OTHER
OFF
n/a
The card will also respond to a lamp test when instigated on the panel to which it is connected.
Figure 83: 32 Zone and 16 Zone Indicator Decals
(See LAB1516.doc on the Web for Slip in Label)l
Fit EOL Termination Link
if Last Module
on Comms Bus
In
Out
Address SW
(See Note)
1
2
3
4
ON
C
N
1
C
N
2
RS485 Control
/ 27VDC
Comms In
Top Card &
PCB Securing Clips
Bottom Card &
PCB Securing Clips
RS485 Control
/ 27VDC
Comms Out
Figure 84: Zone Alarm Mimic Card Rear View showing connectors and Address Switch
Note: See Section 17 for Addressing Details (SW1)