Page 23
4.14.1
Detector loop Isolator Installation
In applications where it is not necessary to use an isolating base for each detector, up to 20 detectors
may be installed between isolating bases.
Note: Refer to Apollo Isolating specifications and guidelines for further details.
If a short circuit or abnormally low impedance occurs, the base isolates the negative supply in the
direction of the fault. When the short circuit is removed the power will automatically be restored.
Note: Isolating base is polarity sensitive.
4.14.2
Loop Isolator calculator
The number of isolating devices on the loop can limit the maximum loop cable length depending on
the type of cable used and the total loop current. Refer to the tables below for reference.
Maximum Cable Length Using 1.5mm². Cable
Number of Isolators
0
5
10
15
20
25
30
35
40
45
50
Loop Current Total (mA
)
MAX CABLE LENGTH USING 1.5mm
²
.
50
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
100
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
150
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
200
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
960
250
1000
1000
1000
1000
973
933
893
853
813
733
733
300
971
931
891
851
811
771
731
691
651
611
571
350
850
810
770
730
690
650
610
570
530
490
450
400
756
716
676
636
596
556
516
476
436
396
356
450
680
640
600
560
520
480
440
400
360
320
280
500
618
578
538
498
458
418
378
338
298
258
218
Maximum Cable Length Using 2.5mm². Cable
Number of Isolators
0
5
10
15
20
25
30
35
40
45
50
Loop Current Total (mA
)
MAX CABLE LENGTH USING 2.5mm
²
.
50
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
100
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
150
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
200
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
250
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
300
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
952
350
1000
1000
1000
1000
1000
1000
1000
950
883
817
750
400
1000
1000
1000
1000
993
926
859
793
726
659
593
450
1000
1000
1000
933
867
800
733
667
600
53
467
500
1000
964
897
930
764
697
630
564
497
430
364
4.14.3
Loop Open / Short Circuit.
In the case of an Open Circuit or Short circuit (short circuit isolators used) on the Loop Line the Loop
board provides the ability to drive out from both sides of the loop (In and Out). When these Faults are
repaired / cleared the panel will still report a Loop Fault until a Loop Test is performed on the
appropriate loop.