Page 50
EDIT Z CONFIGURATION
CONFIG: LATCHING
Use < or > to change alarm setting
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 68: Zone Configuration Latching / Non-latching
Use
or
to change the setting
Configuration settings are Latching, Non-Latching, AVF, Self Reset ( 0 to 99 seconds ). After setting
the Configuration the ZONE I/O GROUPS are programmed.
EDIT Z I/O GROUPS
GROUP1:
GROUP2:
GROUP3:
GROUP4:
GROUP5:
GROUP6:
Enter GROUP NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 69: Zone I/O Groups
After scrolling through the groups and entering what I/O GROUPS will be turned on by what module/s
or device/s in a zone/s the operator is prompted to press
to confirm the entries and / or
changes.
8.9.2
Device
Press
DEVICE:
Use these buttons to
EDIT
and move through wording & numbering
Use these buttons to
MOVE
between fields i.e.: DESC & TYPE and next
parameter
Enter the
and
number then scroll through the following screens.
Press
or
Press
To
EDIT
or
to
DELETE
1.
EDIT LxSx DESCRIPTION AND TYPE STRING.
Edit then.
Press
e.g.:
DESC
Loop 1 Sensor 1
TYPE
SMOKE
2.
Allocate / Edit the Device to a Zone and set the device type then.
Press
e.g.: XP95 Photo, XP95 Heat etc-
3.
Set /Edit and display the Output Configurations or options then.
Press
e.g.: Latching, AVF, Non-latching etc