Page 44
8.3
Day/Night
Press
The
DAY-NIGHT SETTINGS
screen will appear. Time entry is the same as setting the
“Time” facility. Note this Function is available at Access Level 3 only.
Press
To enter the
DAY ON
time.
Press
To enter the
NIGHT ON
time.
Press
To ENABLE / DISABLE
DAY-NIGHT SETTINGS
–
CURRENTLY DISABLED
DAY ON TIME 08:00 NIGHT ON TIME 18:00
0:DAY TIME 1:NIGHT TIME 2:ENABLE
SELECT NO
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 56: DAY-NIGHT SETTINGS Menu
For this Function to have control it must be
ENABLED
by press
Re-pressing
will toggle to
DISABLE
.
8.4
Logs
Press
to access the
EVENT LOG MENU
will be displayed.
The
LOGS MENU
allows the operator to select and view the events that have occurred.
EVENT LOG MENU (MAXIMUM SIZE = 2000)
0:ALARM 1:FAULT 2:DISABLE 3:SYSTEM
4:I/O 5. ERASE ALL LOGS 6. WDOG
SELECT NO
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 57: DAY-NIGHT SETTINGS Menu
Once the type of log is selected, e.g. FAULT, each entry can be viewed by stepping through them
using the
buttons
Note: Pressing
and
require access level 3.
The type of log, number and totals logged, date and time of the ALARM, FAULT, DISABLE, SYSTEM
or I/O as well as device information will be displayed. The SYSTEM screen displays events and
watchdog activity. From these screens the operator can select two other facilities, they are;
PRINT ENTRY
will print out the displayed information if a printer is installed, or
SHOW OPTIONS
allows the operator to select how the Logs are viewed
.
To
VIEW BY
ENTRY NUMBER
,
to
VIEW BY DATE
or
to
PRINT MULTIPLE ENTRIES
. In
each case the screen will ask for the appropriate information (ENTRY NUMBER or DATE) to be
entered before the selected option will be displayed.