11
Modem / Programming / Debug Interfacing
The modem I/O port is a Dual DB9 connector (CN8 situated on the lower left hand corner of the Main
Board BRD86MBA) that is normally used for programming of the FACP via the serial port of a PC or
Laptop. There is also a USB connector (CN25) provided to allow programming of the FACP from a
USB port of a PC.
PIN 1
T D
R D
SHIELD
CN27 - 10 WAY IDC
CONNECTOR
O U T
BUZZER
INHIBIT
BUZZER
RS485 EOL
COMMS1 RS232/MODEM
(BOTTOM)
EXPANSION PANEL
EXPANSION LEDS
E
X
P
A
N
S
IO
N
M
O
D
U
L
E
COMMS2 RS232 (TOP)
RS232
COMMS 2
27V IN
RN17
RN16
C90
C
8
9
CN8
R64
CN27
ZDN2
R19
CN25
U32
R25
C N 9
R20
Q5
C N 2
+
BZ1
C N 3
C83
RN6
LK3
R56
TH1
CN21
C82
LK2
R58
R57
R55
CN28
COMMS 3 USB
MAIN BOARD BRD86MBA
NOTE: CN8 (TOP)
& CN27 ARE BOTH
COMMS 2 IN CFM
The Controller also has the required hand shaking to support connection to a Modem, thus allowing
the FACP to be programmed from a remote site that has an established telephone connection. This
allows the system software to be upgraded by simply transmitting a file via the serial port of the PC or
Modem external to the FACP. Diagnostic facilities are also available via the same connection.
Figure 79: FireFinder PLUS Debug Cable Connections
Figure 80: FireFinder PLUS Debug Cable Connections
Note: the DB9F to DB9F cable is not sensitive to which end is plugged in to the FireFinder PLUS
or serial port of the PC or vice versa.
The connections between the PC/Modem and the panel are crossed. i.e. TD connects to RD.
Make sure the
ConfigManagerPlus
program is set to use the port you have connected the cable to
and set up the configuration as follows:
Bits per second:
115200
Data bits:
8
Parity:
None
Stop bits:
1
Flow Control:
None
1
6
2
3
4
5
7
8
9
Tx Data
Rx Data
Signal
Ground
CN8
Plug in DB9
Connector
Note: CN8 is located on the lower
left hand side of the Main Board
COMMS PORT 2
COMMS PORT 1
COMMS PORT 3
Note:
Debug/Notebook
cables are available from
AMPAC
Содержание FireFinder PLUS
Страница 1: ...FireFinder PLUS ...
Страница 4: ...FIRE BRIGADE RESPONSE GUIDE ...
Страница 99: ...Page 92 12 17 3 Panel Interfacing ...
Страница 127: ......
Страница 128: ...UNCONTROLLED DOCUMENT NOTE Due to AMPAC s commitment to continuous improvement specifications may change without notice ...