Page 85
12.16.5
Interface Wiring
Monitored Inputs TB2 1 & 2
Solenoid & Metron
This input relies on N/O or N/C relay contacts used in conjunction with 22K
EOL and 4K7
series
resistors. The type of agent release mechanism and contacts used has to be set in the Programming
Menu for the input to function as per the manufacturers specifications and be in accordance with the
relevant Standard.
Figure 108:
Solenoid, Metron PSW, LPSW and “LOCK” TB3 Wiring
LPSW & Lock
These inputs are also monitored and should be wired as shown above
Figure 109 Gas Fired Wiring
Figure 110: System Inoperative Wiring
As can be seen from above the;
1.
Gas Fired Output can be wired to any interfacing or 1A monitoring circuit that requires a closed
relay contact to indicate a change of state. This could be a relay or a solid state device.
2.
System Inoperative Outputs 27V @ 1A to supply interfacing, signage and aural alarms to
indicate the system has been taken out of service or has developed a fault.
Stage 1, Stage 2
Figure 111: Stage 1 & 2 Wiring
Note: The PSW, LPSW & the Interlock Mechanisms are all
mounted onto the top of the cylinder containing the Agent
Termination
Board
+ -
4K7
22K
EOL
Agent
Distribution
4K7
22K EOL
LPSW
LOCK
4K7
22K EOL
P S W
+ - + -
MAIN / RESERVE
RELEASE
To TB7
MAIN or
RESERVE
Release
Agent
MAIN
RESV
+ -
10K EOL
Solenoid
+ -
TB7
1
2
To Monitoring
Interface / Device
0 V
RL2A
TB3
= MOV
35V
*
*
*
To Sys
Inop Mon
+
-
System Inoperative
1
2
0 V
RL1A
TB4
+27V Current
Limited to1A
- ( + )
+ ( - )
*
0 V
TB5 = Stage 1
TB6 = Stage 2
= MOV
35V
*
*
+ve
-ve
10K
EOL
1 or 2 Way
Signage
To audible / visual
device or interface
*
Stage 1 or
Stage 2
RL3A
RL5A
RL4B
RL4A
RL6A
Termination Board Relays
RL6B
1
2
3
4
The above circuitry applies to both
TB5 ( Stage 1 ) and TB6 ( Stage 2 )
TB5 / 6