FIRE BRIGADE RESPONSE GUIDE
Responding to a Fire
Access Level 1
The
indicator will be illuminated. The applicable zone
indicator will also be illuminated if a Zone Board is installed otherwise details of the Loop, Sensor and
Zones in alarm are displayed on the LCD as follows.
FIRST ALARM: L1 D1 Z1 15:31
D.DSC:Loop 1 Sensor 1
Z.DCS:Zone 1
LAST ALARM: L4 D49 Z5 15:31
D.DSC:Loop 4 Sensor 49
Z.DCS:Zone 5 Depend C
PRESS PREVIOUS/NEXT TO VIEW OTHER ALARMS
AC:2Z ALM:5 PALM:0 FLT:0 DIS:0
This control is used to silence the local buzzer. Pressing this button will silence the
panel buzzer, which sounds whenever there is a fire alarm or fault. The sound for a fire
alarm is a steady sound where as for a fault it is intermittent.
Access Level 2
–
Default Access level when the door is opened.
When the alarm devices are active (FACP is in the fire condition), activating this
control will silence all alarms excluding the External Alarm device.
Activating the control again, will resound the previously silenced alarm devices.
If a new alarm is recognised whilst the alarm devices are “silenced”, then all alarm devices shall
resound.
Note: If Delays to Outputs have been configured, to investigate the delayed Alarm condition press the
“Next” button and “Enter” button.
Previous and Next controls are used to scroll the events on the
LCD. The events being displayed depends on the current
selected view, ie Zone Mode or Device Mode.
W
hen the “SEVERAL ALARMS” indicator is illuminated, then
multiple fire alarms are present on the FACP. In order to view
the alarms the PREVIOUS and NEXT controls are used.
A Zone or Device can be disabled when in an Alarm or Fault condition by pressing the
Disable button.
Note: The Alarm condition takes precedence and no alarms must be present for using
this button to disable faults.
**Note:
The “Disable” button will not clear the Fire Alarm condition. A subsequent “Reset” operation is
required to clear the Fire Alarm condition as per the requirements of AS4428-3:2010 clause 2.2.10.
This control is used to reset the FACP from the fire condition and to clear the system
fault indicator.
When using the Reset button to clear a fire condition, alarm devices must have been
silenced first by means of Alarms Silence / Resound control.