Page 57
12
Expanding the FACP with Compatible FireFinder PLUS Boards
12.1
Ancillary Services
The FACP has been designed such that detectors and/or call points, in addition to giving an alarm and
calling the fire brigade, will close or open circuits of ancillary services by means of relays or similar
devices.
Examples of these services are:
➢
Actuation of fixed fire-extinguishing systems
➢
Closing of windows, smoke and fire doors
➢
Control of ventilating systems
➢
Covering of tanks containing flammable liquids and controlling their valves to isolate the
contents from direct contact with the fire, etc.
To facilitate safe maintenance of these services an option is available that allows for the isolation and
visual indication of the disablement of ancillary services that does not affect the normal operation of
the fire alarm system.
To ensure power to the fire alarm system is not prejudiced in any way, power for the ancillary services
must be included in the calculation of the power supply and battery capacity.
12.2
Compatible FireFinder PLUS Boards
Add- On Module / Board
Max No
Brigade Board
1 Per Controller
8 Zone Conventional Card
15 per Controller
32 Zone Alarm Indicator Card
15 per Controller
8 Way Relay Board
15 per Controller
Smart terminal
30 per Controller
Agent release module
8 per Controller
4 way Fire Fan Module with Reset
15 per Controller
4 way Fan Control (Loop driven)
15 per Controller
8 way Switch and Indicator Card
15 per Controller
16 Way Input Board
15 per Controller
High Level Interface Expander
3 per Controller
8 Way Sounder Board
15 per Controller
Zone Control Card
15 Per Controller
Conventional Network Board
1 Per Controller
Bargraph Display Card ( BDC )
Printer
1 per Controller
Expansion Board
1 per Controller
Network Interface Card
1 per Controller
Apollo / Dual Loop Termination Board
8 Per Controller
Communication Extender Board
1 per Controller
Note:
The Max Numbers of modules/boards that can be installed and configured within the
FACP depends on the cabinet size and the number of Panels in the System.
Note: Refer to individual Product datasheets and installation guides for complete details.