including that the receiver responds to signals from an actuating
device for alarm, tamper, low standby power signals and gives a fault
signal when the supervisory signal condition is absent.
(j) Operation of fault and alarm signals:
Fault and alarm conditions
correctly detect and indicate as the correct. alarm zone, operating
other required indicators, and operate relevant outputs of the CIE.
(k) Mimic panel:
All mimic panels, annunciators, etc., operate
correctly.
(l) Alarm zone controls:
Alarm test, fault test, isolate and reset
facility of each alarm zone operates correctly.
(m) Alarm dependency:
Alarm dependency works correctly and
does not apply to devices listed in Clause 3.3 of AS 1670.1.
(n) CIE response to actuating device operation:
Each actuating
device has operated when tested with a medium suitable for the
device type and the alarm has indicated on the FIP and at the tested
device.
(o) Fault response time:
The response to a fault does not exceed
100 s for each alarm zone circuit.
(p) Alarm response time:
At least one detector in each alarm zone
has been tested and the response to the alarm does not exceed 10 s
or the period specified when dependency on more than one alarm
signal is used.
(q) Supervisory signal response time:
At least one supervisory
device in each alarm zone circuit has been tested and the response
to the supervisory device does not exceed 100 s.
(r) Alarm acknowledgment facility:
Alarm acknowledgement
facilities operate in accordance with the requirements of Clause 3.2
AS 1670.1.
(s) Occupant warning system:
(i) A fault signal is displayed at the CIE when the circuit wiring at the
last speaker or sounder is short or open circuited.
(ii) Each sounder/speaker operates in accordance with the
requirements of Clause 3.22 of AS 1670.1 and a record of the sound
pressure level has been made.
(t) The external alarm indication
: is visible from the main approach
to the building.
(u) Manual call points
(i) Each manual call point operates correctly.
(ii) The activation of manual call points do not cause existing detector
alarm indications to be extinguished.
(iii) Manual call points are not subject to alarm dependency.
(v) Smoke and fire door release:
Each door-release device
operates correctly.
(w) Flame detectors
(i) The number and type of flame detectors provide adequate
protection for the area.