Page 59
12.4
8 Zone Conventional Board
This board (BRD43EZC) has 8 conventional zones. Up to 999 zones max may be configured.
The zones may be used in panel programming and Input / Output programming.
Note 1:
Each Zone circuit MUST be terminated with either a;
➢
3k3 resistor (
Default
)
➢
10uF 50VDC bipolar capacitor
➢
4k7 resistor
➢
6k8 resistor, OR
➢
10k resistor
+ -
Z 1
E
OL
TB1
CN2
CN3
RS485 Control
Comms In
RS485 Control
Comms Out
CN4
CN5
Fit EOL Termination
Link 1 if Last Module
on Comms Bus
1 2 3 4
O N
SW1
ON
Address SW
(see Note 3)
To Zones 1 to 4 + / -
To Zones 5 to 8 + / -
27V IN
+
-
27V OUT
+
-
-
+
-
+
-
+
-
+
-
+
-
+
-
+
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
TB1
TB2
To Zones 5 to 8 + / -
To Zones 1 to 4 + / -
PRESS HERE
TO BREAK
FIRE
ALARM
Maximium of 32
devices per Zone
(See Note 2)
End Of Line
(See Note 1)
EOL
EOL
EOL
EOL
EOL
EOL
EOL
+ -
Z 3
+ -
Z 2
+ -
Z 4
+ -
Z 5
TB2
+ -
Z 7
+ -
Z 6
+ -
Z 8
Figure 82: 8 Zone Conventional Board
Connections
Terminal/s
Function
TB1&2 Terminals 1, 3, 5, 7, 9, 11, 13, 15
TB1&2 Terminals 2, 4, 6, 8, 10, 12, 14, 16
ZONES 1 to 8 +ve
ZONES 1 to 8 -ve
Note 2:
If Diode Bases are used ONLY the 10uF CAP can be used.
Note 3: See Section 17 for Addressing Details (SW1)
Note 4:
Short circuits on the Zone is a “Fault” condition on the FACP NOT an “Alarm”
Note 5:
Hard contact MCP’s will require a 470Ω to 680Ω series activation resistor to generate an
alarm condition and to avoid hard contact MCPS putting the Zone into Short circuit fault
”
Содержание FireFinder PLUS