INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model FS-WST
Addressable Wall Mount Strobe
Notifier by Honeywell
9 Columbia Way Baulkham Hills,NSW 2153
Australia
www.notifier.com.au
SPECIFICATION
Item
Parameter Description
Note
Operating Voltage
DC24V( DC15V~ DC32V)
Avg. Standby Current
<400µA
24VDC, No Communication, No flashing
Alarm Current
<8mA
Alert flash pattern(4.4mA)
Evacuate flash pattern(4.6mA)
Operating Temp
-25
℃
~+70
℃
Humidity 10~95%
R.H.
Non-condensing
Ingress Protection
IP33
IP35(With Water-proof box )
Flash Pattem
2
See table 1: ‘Setting’
Flash Intensity
>1cd
Height 47mm
Diameter 122mm
Weight 156
±
6g
Before installing and using the product, please read the system
wiring and installation manual thoroughly. If the products will
be installed in an existing operational system, inform
the operator
and local authority that the system will be temporarily out of
service, disconnect
power to the control panel before installing the
products.
NOTICE: This manual should be left with the owner/user of this
equipment.
GENERAL
FS-WST is an intelligent addressable AV products designed to
alarm light for emergency events, and be able to communicate
with control panel by intelligent protocol.
It is designed specifically for analogue addressable fire alarm
system and only can be connected to control panels with a
compatible proprietary analogue addressable communication
protocol. It is powered from the loop and can be controlled via
the communication protocol(s). The Wall Mount Version is
compatible with B501 mounting base. Up to 159 addresses are
available via two rotary selector switches. The alarm light can
be tested on field.
INSTALLATION
It must be installed and wired with B501 mounting base.
1.
Verify the product type matches with product drawing.
2.
Set the address via two rotary selector switches. Please
refer to “Address setting”.
3.
Volume and tone setting are realized by 4 digit DIP witch.
On field testing can be tested via DIP switch.
4.
Plug the
Wall Mount Strobe
into B501 mounting base.
5.
Turn the
Wall Mount Strobe
clockwise until it drops into
place.
6.
Continue turning the
Wall Mount Strobe
clockwise to lock it
in place.
Figure 1
SETTING
Address setting
Rotary-decade switches are provided for setting the address
whose range is from 1 to 159. (Default address is 01).
Address is set by turning the switches.
Address is calculated as below formula: Address = TENS *10
+ ONES*1. For instance: Address 05 = 0*10 + 5*1.