background image

1. INTRODUCTION

Pressing on the Ei407 Manual Call Point (Manual Call Point) black spot 

causes all Alarms on RadioLINK Bases and RadioLINK  Alarms to 

sound. This informs the occupants that the building must be evacuated.

The Ei407 Manual Call Point also provides a means to test the 

Alarms without having to reach up to the Alarms on the ceilings, as it 

can be reset with the plastic key (supplied).

We suggest that the plastic key is mounted on a small nail under or 

alongside the Manual Call Point for future use when resetting (as 

shown above). 

2. INSTALLATION

It is recommended that you install all the other RadioLINK Bases / 

Alarms and any other RadioLINK components before installing this 

Manual Call Point.
All RadioLINK units should be located in their final positions before 

House Coding commences.
1. The Manual Call Point should be positioned (approx) 1.2 meters high 

on a wall, in a suitable location on an exit route (avoid locating near 

metal objects).
2. Securely attach the mounting box to the wall using the fixing 

screws supplied.
3. Remove the bottom housing by first pushing in the forked end of 

the key (with arrow side out) into the two slots (see Figure 1). The 

bottom housing should drop down by about 10mm and expose the 

yellow edge on the top of the white element (with the black spot).  

Remove the key, pull the bottom housing down and then lift it up to 

remove (see Figure 2).
4. Next remove the white element by lifting the lower edge (see 

Figure 3).

5.  Connect the built-in battery by sliding the 

battery switch into the “on” position. (see     

Figure 4).
6. Press the House Code switch until the light 

on the front turns on red (see Figure 4) (The 

unit will now send out a coded alarm signal 

and the red light will flash). 
7. Screw the front plate to the wall box 

using the two machine screws provided (see 

Figure 5).
8. Now re-install the white element, yellow 

edge uppermost (see Figure 6).  Replace the 

bottom housing by lining up the two notches 

and carefully pushing it flat - this should 

leave it about 10mm below the bottom edge.  
Now slide the bottom housing upwards (see 

Figure 7).  This resets the switch. The yellow 

edge on the white element should now be 

hidden  (The unit will now send out a coded 

alarm cancel signal). The red light will then       

continue to flash to show it is in House Code 

mode, for the next 15 minutes.

9. Immediately put all other RadioLINK 

Smoke Alarms and other components into 

House Code mode within 10 minutes.

10. In House Code mode, the Manual Call 

Point will now send a radio message every 5 

seconds. All RadioLINK Bases and Smoke/

Heat Alarms within range that are also in 

House Code mode themselves will memorise 

the House Code of the Manual Call Point.  

11. Check that the number of amber light 

flashes (for RadioLINK Bases) or blue light 

flashes (for RadioLINK Smoke Alarms)  

corresponds with the number of units in the 

system (e.g. Bases / Alarms plus Manual 

Call Point). For example, with 3 RadioLINK 

Bases and 1 Manual Call Point you should 

see 4 amber light flashes from each Base. 

(Note: the Manual Call Point flashing red 

light does not indicate the number of units 

in the system. It just flashes rapidly to show 

it is in House Code mode. The Manual Call 

Point is only an RF transmitter and does not 

receive any RF signals). 
12. Remove all the RadioLINK Bases / 

Alarms from House Code mode as described 

in their instruction leaflets.
13. The Manual Call Point will exit the 

House Code mode by itself after approx. 15 

minutes without    further user intervention.

However, this could result in problems 

with nearby systems if their units are 

being House Coded at the same time. If 

this is the case remove the Manual Call 

Point from its mounting box and then 

from House Code mode by pressing and 

holding the code button until the red light 

comes on (i.e. use the same method as 

to enter House Code mode). Release 

the button and the red light will go out, 

indicating that the Manual Call Point has 

exited House Code mode. Re-assemble 

and attach to box as described previously.
Please note that this will cause the Manual 

Call Point to send out a coded alarm signal 

which will activate the RadioLINK Bases 

/ Alarms that have previously been House 

Coded during the installation procedure. 

3. CHECKING & TESTING THE Manual Call Point

The Manual Call Point is an important alarm device and should 

be tested after installation and then weekly (and after prolonged 

absence) to ensure correct operation as follows.
a) Check that the light on the front flashes green every 40 seconds. 

This indicates it has power.
b) Press the black spot and the white element will drop down exposing 

the yellow edge to show it is activated. The light will turn red and stay 

on continuously for 3 seconds and then continue to flash red (every 

20 seconds) for 5 minutes indicating transmission of the alarm signal 

(Note: after 5 minutes the RF alarm signal ceases and therefore the 

smoke alarms will stop alarming. This prevents the batteries in the 

Manual Call Point and the alarm from being depleted).
c) Check the RadioLINK units are now in alarm (If some or all of the 

alarms have not been activated, then the House Coding procedure 

should be repeated. If there are still some problems, see the  

“Troubleshooting RF Link” section on page 4). 
d) The Manual Call Point should be reset with the plastic key provided 

by pushing the forked end (arrow side up) into the slots (see Figure 1

and pulling the bottom housing down. Remove the plastic key. Now 

push the bottom housing firmly against the back and slide upwards.  

This resets the switch. The yellow strip on the white element should 

now be hidden.
e) If the Manual Call Point is not reset the light will flash red every 40 

seconds to remind the user to reset it.
On reset, the alarm cancel signal will be  transmitted (indicated by a 

single red light flash for 3 seconds).
If the light flashes amber every 9 seconds this indicates that the     

batteries are depleted and the Manual Call Point will no longer be able 

to send an alarm signal. The unit must be removed from its location 

Manual Call Point

Model: Ei407

For use with RadioLINK Smoke/Heat Alarms and Bases

House Code Button

BATTERY

ON/OFF SWITCH

Figure 1

Figure 6

Figure 7

Figure 3

Figure 2

Figure 4

1

2

3

Contains vital information on the product’s operation and installation. 

Read and retain carefully. If you are just installing this product the      

manual MUST be given to the householder.

Figure 5

Отзывы: