53
Agilaire 8872 Manual
Chapter 2 Configuration
FLAG TYPE
DESCRIPTION
SOURCE OF FLAG
U
Instantaneous
Analog Underrange
Single reading < negative end of full scale
of analog range, invalidates the base
average.
A
Instantaneous
Math Error
Error executing math pack channel
equation, most commonly divide by zero.
+
Instantaneous
Maximum Reading
Error
Reading > configured “Maximum
Reading”, invalidates the base average.
-
Instantaneous
Minimum Reading
Error
Reading < configured “Minimum Reading”,
invalidates the base average.
R
Instantaneous
Rate of Change Error
Reading changed from one reading to
another > the configured rate of change
limit.
H
Average
High High Limit
Exceeded
Average (e.g., 1m, 1h) value >
configured limit.
L
Average
Low-Low Limit
Exceeded
Average (e.g., 1m, 1h) value >
configured limit.
h
Average
High Limit Exceeded
Average (e.g., 1m, 1h) value , configured
limit.
l
Average
Low Limit Exceeded
Average (e.g., 1m, 1h) value <
configured limit.
J
Average
High High Rate of
Change
Change from previous average > set limit.
j
Average
High rate of change
Change from previous average > set limit.
V
Instantaneous
Digital Information#1
Configured status input pattern detected.
W
Instantaneous
Digital Information#2
Configured status input pattern detected.
X
Instantaneous
Digital Information#3
Configured status input pattern detected.
Y
Instantaneous
Digital Information#4
Configured status input pattern detected.
Z
Instantaneous
Digital Information#5
Configured status input pattern detected.
f
Average
Floor limit exceeded
Average < configured Floor Limit, value
changed to floor value.
c
Average
Ceiling limit exceeded Average > configured Ceiling limit, value
changed to ceiling value.