3.14.3 OUTDOOR RESET MODE
Perform the procedure described for the CONSTANT SETPT MODE and then continue with the
steps described below:
Outdoor Reset Mode Programming
Menu & Option
Action
FIELDADJUST MENU
HEADER SET MODE
Set to
OUTDOOR RESET
RESET RATIO
Enter a different value, if required (default = 1.2). Refer to
Appendix C.
BLDG REF TEMP
Enter the desired Building Reference Temperature.
Default = 70°F (Refer to Appendix C).
CONFIGURATION MENU
FAIL SAFE MODE
Set to
CONSTANT SETPT
if you want to maintain a Constant
Setpointt temperature in the event that the Outdoor Sensor signal
is lost. (Default =
SHUTDOWN)
RELAY MENU
SYS START TEMP
Enter the outdoor temperature below which the system will be
activated.
After completing the “Quick Start” procedure for any of the modes described above, check to
ensure that the “ON” LED is lit. If it is not, press the
ON/OFF
key to activate the ACS.
For further programming details, refer to
Chapter 4
.