AERCO Control System (ACS)
APPENDIX B:
Status and Fault Messages
Page 92 of 139
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
11/22/2017
GF-131
Phone: 800-526-0288
OMM-0081_0F
B.2 C-MORE STATUS AND FAULT MESSAGES
TABLE B-2: C-More Status and Fault Messages
Code
Message
Description
1
DISABLED
HH:MM pm MM/DD/YY
Displayed if ON/OFF switch is set to OFF. The
display also shows the time and date that the unit was
disabled.
2
STANDBY
Displayed when ON/OFF switch is in the ON position,
but there is no demand for heat. The time and date
are also displayed.
3
DEMAND DELAY
XX sec
Displayed if Demand Delay is active.
4
PURGING
XX sec
Displayed during the purge cycle during startup. The
duration of the purge cycle counts up in seconds.
5
IGNITION TRIAL
XX sec
Displayed during ignition trial of startup sequence.
The duration of cycle counts up in seconds.
6
FLAME PROVEN
Displayed after flame has been detected for a period
of 2 seconds. Initially, the flame strength is shown in
%. After 5 seconds has elapsed, the time and date
are shown in place of flame strength.
7
WARMUP
XX sec
Displayed for 2 minutes during the initial warm-up
only.
8
HIGH WATER TEMP
SWITCH OPEN
The High Water Temperature Limit Switch is open.
9
LOW WATER
LEVEL
The Water Level Control board is indicating low water level.
10
LOW GAS
PRESSURE
The Low Gas Pressure Limit Switch is open.
11
HIGH GAS
PRESSURE
The High Gas Pressure Limit Switch is open.
12
INTERLOCK
OPEN
The Remote Interlock is open.
13
DELAYED
INTERLOCK OPEN
The Delayed Interlock is open.
14
AIRFLOW FAULT
DURING PURGE
The Blower Proof Switch opened during purge.
15
SSOV FAULT
DURING PURGE
The SSOV switch opened during purge.