3.12.4 AUX RELAY OPEN
The
AUX RELAY OPEN
setting is the Percent Level output below which the AUX Relay will
open if it was closed due to the conditions described by the AUX RELAY CLOSE setting.
3.12.5 AUX RELAY CLOSE
This determines the condition for which the AUX relay will close. If 100% FIRE RATE is
selected, the AUX relay will close when all available boilers are firing at 100%. If 100% AND
OFF (default) is selected, it will close when all available boilers are firing at 100% as well as
when no boilers are available and the boiler plant is below setpoint. This relay can trigger
emergency heat in the latter case.
3.12.6 FAULT ALRM RELAY
This setting tells the ACS which faults should activate the fault alarm relay. The default is
ALL
FAULTS
. If
NO INTERLOCK
is selected, the Fault Alarm Relay will not activate when the
interlocks are opened, however the ACS will still shut down all boilers. If
INTERLOCK 2
is
selected, the Fault Alarm Relay will only activate when Interlock 2 is opened and not when
Interlock 1 is opened. Similarly, when
INTERLOCK 1
is selected, the fault alarm relay will only
activate when Interlock 1 is opened and not when Interlock 2 is opened.
3.12.7 FAULT ALARM BLRS
This selection tells the ACS whether to activate the fault alarm relay if a boiler connected to it is
faulted.
3.12.8 FAULT ALRM CLEAR
Selecting MANUAL will latch the fault alarm relay if a fault condition occurs and goes away. The
CLEAR key must be pushed to deactivate the relay. If set to AUTOMATIC, the fault relay will
open when the fault condition goes away.
CALIBRATION MENU
3.12
The options contained in this Menu should only be used by factory-trained personnel, since it
contains options that could adversely affect system operation if incorrectly set.
NOTE
The Level 2 Password (
6817
) must be entered in order to view or
change options in the Calibration Menu.
3.13.1 HDR SENS OFFSET
This option sets the offset temperature value that is added to the displayed Header Sensor
temperature in the event that it is different from a trusted reference Header temperature reading
and needs calibration. Be sure the Header Sensor is properly installed before adjusting this
offset value. The allowable offset range is ±10°F
3.13.2 OUTD SENS OFFSET
This offset value is added to the Outdoor Sensor temperature displayed in case it is different
from a trusted reference outdoor temperature reading and needs calibration. Be sure the
Outdoor sensor is properly installed before adjusting this value. The allowable offset range is
±10°F.