AERCO Control System (ACS)
CHAPTER 3
: Operation
11/22/2017
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
Page 65 of 139
OMM-0081_0F
Phone: 800-526-0288
GF-131
3.14.2 REMOTE SETPT MODE:
Perform the procedure described for the CONSTANT SETPT MODE and then continue with the
steps described below:
Remote Setpoint Mode Programming
Menu & Option
Action
FIELD ADJUST MENU
HEADER SET MODE
Set to
REMOTE SETPT
HDR HIGH LIMIT
Enter the maximum temperature for the Remote Setpoint input
(this will be the temperature equivalent to a 20 mA input) Default
= 200°F
HDR LOW LIMIT
Enter the minimum temperature for the Remote Setpoint input
(this will be the temperature equivalent to a 4 mA input) Default =
40°F
REMOTE SIGNAL
Select 4-20 mA (default) or MODBUS
CONFIGURATION MENU
FAIL SAFE MODE
Set to
CONSTANT SETPT
if you want to maintain a Constant
Setpoint temperature in the event that the Remote signal is lost.
(Default =
SHUTDOWN)