AERCO Control System (ACS)
CHAPTER 4
: Programing ACS Operating Modes
Page 70 of 139
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
11/22/2017
GF-131
Phone: 800-526-0288
OMM-0081_0F
4.2.5 Entering System Start Temperature
In order to set up the Outdoor Reset Mode, the System Start Temperature must be entered. The
System Start Temperature is the outside air temperature at which the boiler plant begins to
operate. The factory default value for the System Start Temperature (
SYS START TEMP
) is
70°F. However, temperatures from 32°F to 120°F can be selected using the
▲ and ▼ arrow
keys on the ACS keypad. Proceed as shown below:
Entering System Start Temperature
1.
Using the ▲ or ▼ arrow key on the keypad, scroll through the Configuration Menu until
BLR START LEVEL
is displayed along with the current setting (default = 20%).
2.
If the desired Boiler Start Level
is not displayed, press the
CHANGE
key. The display
will switch to to a reverse video format.
3.
Select the desired Boiler Start Level using the ▲ or ▼ arrow key.
4.
Press the
ENTER
key to store the changed Start Level.. The reverse video display will
revert to the normal VFD display format.
5.
Next, scroll through the menu until the
BLR STOP LEVEL
is displayed along with the
current setting (default = 16%).
6.
If the desired Boiler Stop Level
is not displayed, repeat steps 2, 3 and 4 above and enter
the desired Stop Level.
4.2.6 Entering Boiler Start and Boiler Stop Levels
The Boiler (BLR) Start and Boiler Stop Levels are also entered in the Configuration Menu. Refer
to Appendix I to determine the correct Start and Stop levels for your installation. Enter the
appropriate values in the Configuration Menu as shown below:
Entering Boiler Start & Boiler Stop Levels
1.
Press the
MENU
key until
RELAY MENU
appears in the display.
2.
Press the ▲ arrow key once.
SYS START TEMP
will be displayed along with the current
setting for the System Start Temperature.
3.
Press the
CHANGE
key to change the displayed temperature. The display will switch to
a reverse video format.
4.
Select the desired System Start temperature using the ▲ or ▼ arrow key.
5.
Press the
ENTER
key to store the changed temperature. The reverse video display will
revert to the normal VFD display format.