AERCO Control System (ACS)
APPENDIX A:
ACS Menus
11/22/2017
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
Page 87 of 139
OMM-0081_0F
Phone: 800-526-0288
GF-131
TABLE A-1: ACS Menus
Menu Level & Option
Available Choices Or Limits
Default
Minimum
Maximum
SUN
OFFS TEMP
-50.0°F
50.0°F
00.0
SUN ON HOUR
00
23
00
SUN ON MINUTE
00
59
00
SUN OFF HOUR
00
23
00
SUN OFF MINUTE
00
59
00
Etc., Up To:
SAT OFF MINUTE
00
59
00
OFFSET ENABLE
OFF, ON
OFF
SUN OFFS TEMP
-50.0°F
50.0°F
00.0
SUN ON HOUR
00
23
00
SUN ON MINUTE
00
59
00
SUN OFF HOUR
00
23
00
SUN OFF MINUTE
00
59
00
Etc., Up To:
SAT OFF MINUTE
00
59
00
CONFIGURATION MENU
BOILER CONTROL SELECT
OFF, CMORE, BCM
OFF
BOILER OP MODE
SEQUENTIAL MODE,
PARALLEL MODE
SEQUENTIAL
MODE
SYS INTLK CONFIG
START ENABLED,
ALWAYS ENABLED
START ENABLED
BLR START LEVEL
001%
100%
020%
BLR STOP LEVEL
001%
040%
016%
MAX POWER INPUT
050%
100%
100%
FAIL SAFE MODE
SHUTDOWN,
CONSTANT SETPOINT
SHUTDOWN
LEAD BOILER SELECT
NONE, NETW BOILER 1
NONE
LAST BOILER SELECT
NONE, NETW BOILER 1,
NETW BOILER 2, Etc., Up To:
NETW BOILER 32
NONE
ROTATE TIME
0 to 999 HOURS
168 HOURS
RETURN SENSOR MODE
OFF, NORMAL, DHW/TANK TEMP
OFF
PLANT DELTA-T LIMIT
10°F TO 100°F
40°F