Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
59 (0x003B)
Offset Enable
0 or 1
0 = Disabled
1 = Enabled
Default = 0
(Disabled)
60 (0x003C)
Header Temp Offset
-10 to 10°F
Default = 0°F
61 (0x003D)
System Start Interlock
1, 2 or 3
1 = Intlk1 Opens Start Relay
2 = Intlk2 Opens Start Relay
3 = Either Intlk Opens Start
Relay
Default = 1
(Intlk 1)
62 (0x003E) Thru
69 (0x0045)
(Reserved)
70 (0x0046)
Offset Off Time Sun. – Minutes
0 to 59 Minutes
Default = 0
71 (0x0047)
Offset Off Time Mon. – Minutes
0 to 59 Minutes
Default = 0
72 (0x0048)
Offset Off Time Tue.– Minutes
0 to 59 Minutes
Default = 0
73 (0x0049)
Offset Off Time Wed.– Minutes
0 to 59 Minutes
Default = 0
74 (0x004A)
Offset Off Time Thu – Minutes
0 to 59 Minutes
Default = 0
75 (0x004B)
Offset Off Time
Fri. – Minutes
0 to 59 Minutes
Default = 0
76 (0x004C)
Offset Off Time
Sat. – Minutes
0 to 59 Minutes
Default = 0
77 (0x004D)
Offset Off Time
Sun. – Hours
0 to 23 Hours
Default = 0
78 (0x004E)
Offset Off Time
Mon. – Hours
0 to 23 Hours
Default = 0
79 (0x004F)
Offset Off Time
Tue. – Hours
0 to 23 Hours
Default = 0
80 (0x0050)
Offset Off Time
Wed. – Hours
0 to 23 Hours
Default = 0
81 (0x0051)
Offset Off Time
Thu. – Hours
0 to 23 Hours
Default = 0
82 (0x0052)
Offset Off Time
Fri. – Hours
0 to 23 Hours
Default = 0
83 (0x0053)
Offset Off Time
Sat. – Hours
0 to 23 Hours
Default = 0
84 (0x0054)