Section 3 - Installing the Control
3-11
CONTROL
PANEL
4297
MODULE
Notes: - Do not use the 4197 module.
- Refer to 4297 instructions for more detailed installation information.
The limits shown below supercede the limits described in the 4297 instructions.
- Do not connect 4297 modules in series.
- - -
RPM
- - -
Input Polling Loop
Extension Polling Loop
RPM
RPM
RPM
Extension Loop Limits:
- Same as for the input polling loop.
Input Loop Limits:
- 128mA max. No more than 64mA
on any individual wire run.
- No individual wire run may exceed:
Gauge Length
#22
#20
#18
#16
650 ft.
950 ft.
1500 ft.
2400 ft.
- Total length of all wire runs combined cannot
exceed 4000 ft. (2000 ft. if using unshielded
wire in conduit or shielded wire).
Combined Input and Extension Polling Loop Limits:
- No more than 119 devices combined.
- Total length of all wire runs on all loops combined can-
not exceed 6400 ft. (3200 ft. if using unshielded wire in
conduit or shielded wire)
Figure 3-17: Polling Loop Connections Using One
4297 Extender Module
Polling Loop Supervision
A short on the polling loop is indicated by a trouble on
zone 997 and reports as a trouble condition only. If
annunciation is desired, program the zone as type 05.
If a device on the polling loop fails (the panel cannot
"see" that device), the system displays a trouble
condition for all zones on that device. If the panel is
armed when a device fails, and the zone is a burglary
zone, the will go into alarm
A trouble on zone 997 prevents a partition from
being armed, unless all polling loop zones on
that partition are bypassed.
CONTROL
PANEL
4297
4297
4297
Input Polling
Loop
Notes:
- Do not use 4197 module.
- Refer to 4297 instructions for more detailed installation information.
The Limits shown below supercede the limits described in the 4297 instructions.
- Do not connect 4297 modules in series.
Extension Loop #1
Extension Loop #2
Extension Loop #8
- - -
- - -
- - -
Up to 8 modules may be connected
in parallel. Extension loops will be
electrically isolated if blue jumper
on each 4297 is left in tact.
Combined Input and Extension Loop Limits:
- No more than 119 devices combined on all loops
- To calculate the maximum wire run allowed on each extension loop:
1. Determine the total wire length of all input loops combined.
2. Subtract this number from 6400 ft. (3200 ft. for shielded cable or
unshielded cable in conduit).
The result is the maximum wire run length for each extension loop.
- - -
RPM
RPM
RPM
RPM
RPM
RPM
- - -
Extension Loop Limits:
Each individual loop has the
same limits as the input loop.
}
Figure 3-18: Polling Loop Connections Using
Multiple Extender Modules
NOTE: The input loop limits stated in Figure 3-17
apply to Figure 3-18 as well.
Wireless Zone Expansion
UL
Wireless devices may not be used in UL
installations.
The following table lists the receivers that may be used
and the number of zones they support.
5800 Series Receivers
Receiver Zones
5881L
up to 8
5881M
up to 16
5881H
up to 128
In Canada, 5800 systems must use 5882
Series receivers: 5882L/5882H. Information to
the 5881 Receivers applies as well to the 5882
Receivers. Both receivers use the same
transmitters.
RF System Operation and Supervision
The 5800 RF system operation has the following
characteristics:
•
The receiver responds to a 345MHz USA; 315MHz
in Canada frequency.
•
The receiver has a nominal range of 200 feet.
•
Supervised transmitters send a supervisory signal
every 70-90 minutes.
•
Zones 988 and 990 are used to supervise the RF
reception of receivers 2 and 1, respectively. The
reception is supervised for two conditions:
1. The receiver goes “deaf” (does not hear from
any of its transmitters) within a programmed
interval of time (defined by program field
1*30).
2.
Proper RF reception is impeded (i.e., by
jamming or other RF interference). The
control checks for this condition every 45
seconds.
Содержание Vista-128B PLUS
Страница 2: ......
Страница 8: ...viii...
Страница 100: ...VISTA 128B PLUS Installation and Setup Guide 6 18...
Страница 106: ...VISTA 128B PLUS Installation and Setup Guide 8 2...
Страница 112: ...VISTA 128B PLUS Installation and Setup Guide 9 6...
Страница 124: ...VISTA 128B PLUS Installation and Setup Guide C 2...
Страница 128: ...VISTA 128B PLUS Installation and Setup Guide D 4...
Страница 138: ...l K4968 11 00 165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION...