Section 3 - Installing the Control
3-15
SWITCH
4 2 0 4 A D D R E S S S E T T I N G S
POSITION
("—" means "OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
3
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
4
ON
ON
ON
ON
—
—
—
—
ON
ON
ON
ON
—
—
—
—
5
ON
ON
ON
ON
ON
ON
ON
ON
—
—
—
—
—
—
—
—
ON
1
2345
➞
➞
➞
➞
➞
13
14
15
16
C
NC
NO
OFF
➞
ON
➞
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
➞ ➞
COVER TAMPER (REED) SWITCH
➞➞
TB1
4204
TB2
4-PIN CONSOLE PLUG
➞➞
12
11
10
9
8
7
6
5
4
3
2
1
C
NC
NO
C
NC
NO
C
NC
NO
▲
RELAY
3
RELAY
2
RELAY
1
RELAY
4
TYPICAL
(SHOWN "OFF")
EITHER OR BOTH
CAN BE USED
➞➞
➞
➞
DATA IN
FROM CONTROL
(–) GROUND
DATA OUT
TO CONTROL
(+) 12V
YEL
BLK
GRN
RED
Figure 3-20: 4204 Relay Module
SWITCH
4 2 0 4 C F A D D R E S S S E T T I N G S
POSITION
("—" means "OFF")
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
ON
—
3
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
ON
ON
—
—
4
ON
ON
ON
ON
—
—
—
—
ON
ON
ON
ON
—
—
—
—
5
ON
ON
ON
ON
ON
ON
ON
ON
—
—
—
—
—
—
—
—
ON
1
2345
➞
➞
➞
➞
➞
OFF
➞
ON
➞
13
14
15
16
NC
NC
DIP SWITCH
FOR SETTING DEVICE
ADDRESS AND
ENABLING/DISABLING
TAMPER
➞
➞
COVER TAMPER (REED) SWITCH
➞➞
TB1
TB2
4-PIN CONSOLE PLUG
➞➞
12
11
10
9
8
7
6
5
4
3
2
1
NC
NC
NC
NC
▲
EITHER OR BOTH
CAN BE USED
➞➞
➞
➞
DATA IN
FROM CONTROL
(–) GROUND
DATA OUT
TO CONTROL
YEL
BLK
GRN
RED
(+) 12V; SUPPLIES POWER TO MODULE
CIRCUITRY (INCLUDING NOTIFICATION
APPLIANCE RELAY COILS). CURRENT
DRAIN AT 12V IS: 25 mA + (80 mA PER
ACTIVE OUTPUT)
NOTIFICATION APPLIANCE AND
CONSOLE DATA OUTPUTS ARE
POWER LIMITED
–
+
NOTIFICATION
APPLIANCE B
2K EOLR
#610-7
POLARIZED
NOTIFICATION
APPLIANCE
–
+
NOTIFICATION
APPLIANCE A
2K EOLR
#610-7
}
–
+
POWER FOR
NOTIFICATION APPLIANCE A,
NOTIFICATION APPLIANCE B
8-28VDC OR VFW. UP TO 2.4A
DEPENDING ON BELL CURRENT
- ALARM POLARITY
SHOWN
- EACH OUTPUT
PROVIDES
STYLE Y
SUPERVISION
- EACH OUTPUT
RATED 1.2A MAX
- USE
NOTIFICATION
APPLIANCES
COMPATIBLE
WITH
NOTIFICATION
APPLIANCE
POWER SUPPLY
VOLTAGE
RATING
Figure 3-21: 4204CF Relay Module
Installing the FSA Modules
The 8-zone LED Fire System Annunciator FSA-8 and
24-zone LED Fire System Annunciator FSA-24 enable a
fire response unit to identify quickly the point/zone of a
fire. These indicators may be used for other functions
as well, such as status indication. A maximum of 4 FSA
modules, in any combination, can be supported.
The FSA module will not operate until the
device address you have set the DIP
switches for is enabled in the control’s
Device Programming in the #93 Menu
Mode.
To install the FSA module, refer to Figure 3-22 and
perform the following steps:
Step Action
1
Set the FSA module’s DIP switches for a
device address between 08 and 23. See the
module’s instructions for the DIP switch
table.
Do not use an address being used by another
device (keypads, RF receivers, etc.).
Step Action
2
Mount the FSA module horizontally to a
duplex box (quad box for FSA-24).
3
Connect the module to the control’s keypad
terminals (6, 7, 8, and 9).
0 0 0 0 0
ECP Bus
Dip Switch
Optional
Keyswitch
Connection
SIDE
VIEW
All Switches shown
in Up position.
(ECP Address 23)
Terminal
Block
Connect to
Keypad
Terminals
Figure 3-22: Wiring the FSA Module
Installing 4101SN Relay Modules
The 4101SN V-Plex Single Output Relay Module is a
serial number polling loop output device. The 4101SN
features the following:
•
Form C relay contacts rated at 2A, 28VAC/VDC
with contact supervision.
The position of the relay is supervised, but not
the actual external contact wiring.
•
One class B/style B EOLR-supervised auxiliary
input zone.
•
Operating power and communication with control
panels via the V-Plex polling loop.
•
Electronics mounted in a small plastic case with
tamper-protected cover.
Connect the device to the polling loop, terminals 24 (+)
and 25 (-). Be sure to observe polarity
Installing the 4300 Transformer
Powerline Carrier devices are controlled by signals sent
through the premises’ electrical wiring via a 4300
transformer. If you are using Powerline Carrier
devices, a 4300 transformer must be used in place of
the regular system transformer.
Powerline Carrier devices (such as X-10, ACT, Leviton)
are either plugged into standard AC outlets or wired
into the AC electrical system by a licensed electrician,
depending on the type of device used. They respond to
“on” and “off” commands sent from the panel through
the 4300 transformer to the receiving devices.
Note each device’s House and Unit Code
setup, as these codes will be used to program
the devices in
Output Programming in #93
Menu Mode described in the Programming
Guide.
To connect the 4300 transformer, see Connecting the
Transformer, later in this section.
Содержание Vista-128B PLUS
Страница 2: ......
Страница 8: ...viii...
Страница 100: ...VISTA 128B PLUS Installation and Setup Guide 6 18...
Страница 106: ...VISTA 128B PLUS Installation and Setup Guide 8 2...
Страница 112: ...VISTA 128B PLUS Installation and Setup Guide 9 6...
Страница 124: ...VISTA 128B PLUS Installation and Setup Guide C 2...
Страница 128: ...VISTA 128B PLUS Installation and Setup Guide D 4...
Страница 138: ...l K4968 11 00 165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION...