ASSEMBLED
IN MEXICO
+
+
-
N.C.
N.C.
N.O.
2k EOLR
(note 1)
2k EOLR
(note 1)
+
-
+
-
+
-
BELL
SIREN
NO CONNECTION
TRANSFORMER
16.5VAC, 40VA
ADEMCO No.1361
(IN CANADA
USE No. 1361CN)
or 4300 IF
X-10 DEVICES
WILL BE USED
Connect to
24hr. 120VAC,
60 Hz Outlet
Red
Blk
Grn
Yel
REMOTE KEYPAD
Use 6137/6128
or 6139
(Addressable keypads) only
+
+
-
N.C.
N.C.
2k EOLR
(note 1)
2k EOLR
(note 1)
+
+
-
N.C.
+
+
-
N.C.
N.C.
2k EOLR
(note 1,4)
(note 6)
TIP
(BROW
N)
RIN
G
(GRAY)
TIP
(G
REEN) RING
(RED)
Handset
Incoming
Phone Line
Telephone connections
using Ademco No. 620
RJ31X direct connect
cord.
EARTH GROUND
Connect to good earth
ground to maintain im-
munity to transients.
See Instructions for
proper grounding.
SMOKE
4208U
RPM
4191SN
PIR
Polling loop rating: 128mA max.
See Installation and Setup Guide for
maximum number of devices supported
and maximum wire run length
VISTA-128B PLUS
SUMMARY OF CONNECTIONS
USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS
Zone resistance (Excluding EOLR):
ZONE 1,8: 100 OHMS MAXIMUM
ALL OTHER ZONES: 300 OHMS MAXIMUM
ZONE 1
ZONE 2 ZONE 3
ZONE 4 ZONE 5
ZONE 6 ZONE 7
ZONE 8 ZONE 9
2-WIRE SMOKE
DETECTOR LOOP
(Also supports NO/NC Burg contacts)
POLLING LOOP
LATCHING TYPE GLASS
BREAK DETECTOR LOOP
Data in
Data out
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
RED (+)
BLK (-)
Connect to
12VDC, 4AH
or 12VDC, 7AH
GEL CELL
BATTERY
CHARGING
VOLTAGE
13.7VDC
See
Installation
and Set up Guide
for required
capacity
Replace
every
3 years
NOTE:
WHEN POWERING UP
THE PANEL, PLUG THE
TRANSFORMER IN BEFORE
CONNECTING THE BATTERY.
See Installation Instructions
for max # of keypads
and for max wire run length.
ALARM SOUNDER OUTPUT 10VDC - 13.8VDC
AUXILARY POWER OUTPUT
9.6VDC - 13.8VDC,
750mA maximum
Note: Include current drawn
by keypads and polling loop
devices when making
auxiliary power calculations.
+
-
NOTES:
1. Zone 1 may be selected for EOLR supervised
or normally closed (no EOLR) operation via
cut jumper. (Cut red jumper for normally closed
operation. Do not cut for Fire Usage). Zones 2-8
may be selected for either operation via program
field *41.
Zone 1 supports 2-wire smoke detectors.
See Installation and Setup Guide for recommended
type and maximum number of detectors supported.
2.
Zone 7 may be used for remote keyswitch
arming/disarming. See Installation and Setup Guide
for wiring instructions.
3.
Zone 8 supports 2-wire latching type glass break detectors.
See Installation and Setup Guide for recommended type
and maximum number of detectors supported.
Cut blue jumper to disable supervision of alarm sounder output.
Leave jumper intact to supervise output. (See Installation and
Setup Guide for Programming and Wiring Instructions).
Zone 9 may be used for RS232 input.
4.
1 2 3 4 5 6 7 8 9
1. Not Used
2. Ground-
3. Out 1 (Ground Start)
4. Ground-
5. Out 2 (fire)
6. Ground-
7. Out 3 (burg/aud. panic)
8. Ground
9. Out 4 (silent panic/
duress)
Optional programming:
Out 1: Smoke Detector Reset
Out 2: Armed LED
Out 4: Ready LED
Ratings for Out 1:
Active: 10VDC-13.8VDC through 4k OHMS
Not Active: 100 OHMS to ground
Ratings for out 2-4:
Active: 10VDC-13.8VDC through 5k OHMS
Not Active: 1k OHMS to ground
N.C.
N.O.
N.O.
N.O.
2k EOLR
(note 1,2)
N.O.
N.O.
N.O.
N.C.
N.O.
2k EOLR
(note 1)
2k EOLR
(note 1,3)
N.C.
+
-
J7
GLASS
BREAK
1 2 3 4 5 6 7 8 9
J8
MAKE CONNECTIONS USING
No. 4142TR CABLE
WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED
Fire
Usage
Burg.
Usage
CONNECTION OF THE FIRE ALARM SIGNAL
TO A FIRE ALARM HEADQUARTERS OR A
CENTRAL STATION SHALL BE PERMITED
ONLY WITH THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION. THE
BURGLAR ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
1. I n 2 (Printer DTR)
2. Ground
3. In 3 (4300 sync)
4. In 4 (4300 sync)
5. Ground
6. Out 5 (4300 data)
7. Out 6 (Printer RXD)
8. Ground
9. Ground
Red Jumper
(note 1)
DOC LOAD NO.: 5
J7 Header J8 Header
BATTERY
TABS
4192SD
SMOKE
WARNING: TO PREVENT
RISK OF ELECTRICAL
SHOCK, DISCONNECT
TELCO JACK BEFORE
SERVICING THIS PANEL.
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72 (NATIONAL FIRE
PROTECTION ASSOC., BATTERYMARCH
PARK. QUINCY, MA. 02269). PRINTED
INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING
AND REPAIR SERVICE IS TO BE
PROVIDED WITH THIS EQUIPMENT.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM.
Zone response time:
ZONES 1: 350mSec-500mSec
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B
THIS DEVICE COMPLIES WITH PART 15 OF
FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE
MAY NOT CAUSE HARMFUL INTERFERENCE, AND
(2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE
RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
(Refer to Installation and Setup Guide for information concerning Direct Wire
Downloading and printer connections.)
Notes For UL Household
Fire Installations
1. Use 12VDC, 14AH battery
2. Maximum auxiliary current,
including polling loop 300mA
3. Combined alarm and auxilary power output
and polling loop current must be limited to 750mA
for UL985 Household Fire Installations.
ALL CIRCUITS ARE
POWER LIMITED.
Blue
Jumper
(note 5)
5.
6.
V128BPLUS-SOC-V0
Содержание Vista-128B PLUS
Страница 2: ......
Страница 8: ...viii...
Страница 100: ...VISTA 128B PLUS Installation and Setup Guide 6 18...
Страница 106: ...VISTA 128B PLUS Installation and Setup Guide 8 2...
Страница 112: ...VISTA 128B PLUS Installation and Setup Guide 9 6...
Страница 124: ...VISTA 128B PLUS Installation and Setup Guide C 2...
Страница 128: ...VISTA 128B PLUS Installation and Setup Guide D 4...
Страница 138: ...l K4968 11 00 165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION...