Section 5 – Data Field Descriptions
5-3
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*23
Multiple Alarms (partition-
specific)
0 = disable
1 = enable
If enabled, allows more than one alarm sounding for a given zone
during an armed period.
NOTE: that multiple alarm soundings will not occur more frequently
than allowed by the programmed alarm sounder duration. This has
no impact on the number of communication messages transmitted.
Must be 1 for UL installations.
*24
Ignore Expansion Zone Tamper
0 = disable (tamper detection)
1 = enable (no tamper detection)
If disabled, the system monitors the tampers on expansion zones.
NOTE: Only applicable to certain polling loop sensors with tamper
switches or 5800 Series transmitters.
Must be 0 for UL installations.
*25
Burglary Trigger for Response
Type 8
0 = disable
1 = enable
If enabled, allows triggering of the voltage output on Pin 3 of the J7
header to include zone response type 8 (24-hr. auxiliary).
*26
Intelligent Test Report
0 = disable
1 = enable
If enabled, no test report is sent if any other type of report was sent
since the last test report.
If disabled, test reports are sent at the set intervals, regardless of
whether or not any other report has been sent.
Must be 0 for UL applications.
*27
Test Report Interval
Enter 0001-9999 for the test report interval in
hours.
Enter 0000 for test reporting.
If a test report is desired, enter a test code in Report Code
Programming in #93 Menu Mode. Set first test report time in field
*83.
Maximum Test report interval is 0024 for UL installations.
*28
Power-Up in Previous State
0 = disable
1 = enable
If enabled, the system, upon power-up, reverts to its status prior to a
complete power loss.
If disabled, the system always powers up in a disarmed state.
NOTE: Neither authority level 0 nor 5 can be used to disarm the
system if the control powers up armed.
Must be 1 for UL applications.
*29
Quick Arm (partition-specific)
0 = disable
1 = enable
If enabled, allows arming of the burglary system in AWAY, STAY,
INSTANT, or MAXIMUM mode by using the [#] key instead of the
user code.
NOTES:
When armed, the system reports closing as User 0 if Open/Close
reporting for User #2 (typically a Master level user) was enabled for
a given partition.
If Quick Arm is used, the Installer Code and Authority Level 5 codes
cannot disarm the system.
TouchTone or Rotary Dial
0 = disable
1 = enable
Select the dialing method for the system
If you select TouchTone, make sure the subscriber has requested and is paying for TouchTone service. Note
that whether or not TouchTone dialing for call placement is permitted, communication by the use of DTMF
signaling (ADEMCO High Speed) will still take place. See field 1*33 for TouchTone w/Rotary backup
*30
*31
PABX Access Code
Enter 00-09; B-F (11-15)
This field is used to enter up to four 2-digit numbers representing
the prefix needed to obtain an outside telco line. If not required,
enter nothing and proceed to next field.
Содержание Vista-128B PLUS
Страница 2: ......
Страница 8: ...viii...
Страница 100: ...VISTA 128B PLUS Installation and Setup Guide 6 18...
Страница 106: ...VISTA 128B PLUS Installation and Setup Guide 8 2...
Страница 112: ...VISTA 128B PLUS Installation and Setup Guide 9 6...
Страница 124: ...VISTA 128B PLUS Installation and Setup Guide C 2...
Страница 128: ...VISTA 128B PLUS Installation and Setup Guide D 4...
Страница 138: ...l K4968 11 00 165 Eileen Way Syosset New York 11791 Copyright 2000 PITTWAY CORPORATION...