Installation & Operation Manual - Model AVR6000
C5
3.
Setting the First Stop:
Press the clutch and using the actuator “U bolt” rotate the actuator
so the valve is in the fully-closed position then release the clutch. Loosen the screw located
on the top of the Stop and slide the Stop against the “U bolt” assembly until the two parts
come in contact. Secure the Stop in position by tightening the Phillips head screw.
4.
Setting the Second Stop:
Press the clutch and rotate the actuator in the opposite direction
until the valve is in the fully-open position then release the clutch. Loosen screw located on
the top of the Stop and slide the Stop against the “U bolt” until the two parts come in
contact. Secure the Stop in position by tightening the Phillips head screw (see below).
5.
Apply Power and Run Adaption:
Connect power and signal wires to the actuator. Verify
the power LED is on then press the “Adaption” button and hold for approximately 2
seconds. The actuator will now drive one full cycle to each of its mechanical end Stops.
Upon completion of this cycle the actuator working range (input, feedback and running
time) will be adapted to the actual mechanical angle of rotation.
Rotate by hand
using U-bolt
First Stop Position
Second Stop Position
Rotate by hand
using U-bolt