Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 44
6.5.3.6.5
Device App Configuration
provides a way to check or change the App configuration.
WARNING:
Changing the App Configuration should only be done by a qualified
person that has knowledge of the system, otherwise the airflow and temperature of
room control will be compromised.
6.5.3.6.6
Actuator Feedback Calibration
provides a way to field-calibrate the AVR supply
valve’s actuator feedback signal to correlate with the AVR valve position data point.
WARNING:
Selecting OK will initiate the Actuator Feedback Calibration process
which will include modulating the valve position to fully open and fully closed
therefore it’s important to verify the control override will not adversely impact the
room conditions and occupants of the room prior to beginning.
6.5.3.6.7
Close Active Window After Update
If this item is checked, the Insight program will automatically close a window after
the change has been saved. If this item is not checked, the active window will
remain open until the user closes the window.
6.5.3.6.8
Overrides
Control Overrides provides access to the
Supply
,
Exhaust
, and
Reheat Valve
control
loop outputs for the purpose of overriding the automatic control loop output with a
manually entered value between 0 and 100%. Override Status provides access to
view the active value of all of the AVR control loop commands.