AVR6000 BACnet Points List Continued
BACnet Points List Notes is Continued on the Next Page
DESCRIPTION
PV
UNITS TYPE
Unsubscribed COV Interval
R/W
Seconds
Room Temperature Measurement Adjust
R/W Temperature
Discharge Air Temperature Measurement Adjust
R/W Temperature
General Exhaust Airflow Measurement Adjust
R/W
%
Supply Airflow Measurement Adjust
R/W
%
ARS Slider Temperature Range
R/W Temperature
Constant Supply Airflow Volume
R/W Flow Volume
Constant Exhaust Airflow Volume
R/W Flow Volume
Supply Valve Command Position
R/W/C
%
General Exhaust Valve Command Position
R/W/C
%
Supply Airflow Command Set Point
R/W/C Flow Volume
General Exhaust Airflow Command Set Point
R/W/C Flow Volume
Re-heat Valve Command Position
R/W/C
%
Heating Output Command
R/W/C
%
Cooling Output Command
R/W/C
%
Hardware Digital Input 1 State
R
Binary
Hardware Digital Input 2 State
R
Binary
Supply Airflow Set Point Deviation Alarm State
R
Binary
General Exhaust Airflow Set Point Deviation Alarm State
R
Binary
Room Offset Airflow Set Point Deviation Alarm State
R
Binary
Supply Actuator Position Deviation Alarm
R
Binary
Commit to Flash
(Ref Note 1)
R/W
Binary
Dual Maximum Control Logic
R
Binary
CAV Set Point Status
R
Binary
Mode Status/Select
(Ref Note 2)
1 = Mode 1 Setpoints
2 = Mode 2 Setpoints
3 = Mode 3 Setpoints
4 = Mode 4 Setpoints
Flow Volume Units
1 = CFM
2 = CMS
3 = CMM
4 = CMH
5 = LPS
6 = LPM
Temperature Units
1 = Deg F
2 = Deg C
Room Temperature Alarm Status
1 = Room Temperature Alarm OK
2 = Room Temperature High Alarm
3 = Room Temperature Low Alarm
MSV4
R
Integer
OBJECT ID
AV56
AV57
BI6
BV3
BI1
BI2
BI3
MSV2
MSV3
BV1
Integer
MSV1
Analog Values
Analog Outputs
Binary Inputs
AO6
AO7
AO1
AO2
AO3
AO4
AO5
R/W
Integer
AV51
AV52
AV53
AV54
AV55
R/W/C
BI4
BI5
R/W
Integer
BV2
Binary Values
Multi-State Values
AV50