Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 6
SECTION 2 - SPECIFICATIONS
PERFORMANCE
Accuracy +/- 5% of reading or 5 CFM, whichever is greater
Speed of Response < 1 second control signal response (full stroke cycle time based on actuator type)
Shut-off Leakage Rate Standard: < 1.5% FS at max operating pressure
"S" Option: < 0.5% FS round valves, < 1% FS rectangular valves @ max operating pressure
Max Operating Pressure 3”wc Differential Pressure Across Valve
Min Operating Pressure Reference Section 2.1
Airflow Range Reference Section 2.1
Failure Mode Open, Closed or Last Position (based on actuator type selection)
ENVIRONMENTAL
Temperature Airstream: -20 to 165 deg. F for all Standard Valve Models
-20 to 375 deg. F for the High Temp SS Valve Models
Ambient: -20 to 125 deg. F Storage: -40 to 165 deg. F
Humidity 0 to 90% non-condensing
ELECTRICAL
Input Power 24VAC +/- 20% 50-60Hz or 24 VDC +/- 10%
Max Power for Valve Size 06-24: 30VA or 17W for units with actuator type 3 & 5
13VA or 7W for units with actuator type 7
Max Power for Valve Size 36, 48: 53VA or 30W for units with actuator type 3 & 5
19VA or 12W for units with actuator type 7
Analog Inputs (3) Dedicated Analog Inputs
AI-1 (DTS): Supply Air Discharge Temperature Signal, from Duct Temperature Sensor
Signal Types: (Software Selectable):
Voltage: 0-10v Range, Input Impedance = 100K ohms
Current: 0-20mA Range, Input Impedance = 500 ohms
Resistance: 0-20K ohm Range, 500uA Internal Current Source
AI-2 (GEV/RET): GEX/Return Airflow Volume Signal, From AVT AccuValve
Signal Types: (Software Selectable):
Voltage: 0-10v Range, Input Impedance = 100K ohms
Current: 0-20mA Range, Input Impedance = 500 ohms
AI-3 (FHV): Fume Hood(s) Airflow Volume Signal, from AVC AccuValve(s)
Signal Types: (Software Selectable):
Voltage: 0-10v Range, Input Impedance = 100K ohms
Current: 0-20mA Range, Input Impedance = 500 ohms
Digital Inputs (2) Dedicated Digital Inputs for Setpoint Mode Selectors
Signal Type: Dry Contact Only
Analog Outputs (2) Dedicated Analog Outputs
AO-1 (RHV): Reheat Valve Control Signal, to Reheat Valve Actuator Control Input
AO-2 (GEX/RET): GE/RET Valve Control Signal, to AVT AccuValve Actuator Control Input
Signal Types: (Both AO-1 and AO-2 are Software Selectable):
Voltage: 0-10v Range, Input Impedance = 100K ohms
Current: 0-20mA Range, Input Impedance = 500 ohms
Alarm Output
DPDT Relay, NC/NO Contacts, 1A @ 30vDC or 0.3A @ 125vAC
Max operating voltage = 125VAC or 60 vDC
Max carry current = 1A, Max switching capacity = 37 VA, 30W
NETWORK BACnet MSTP
EIA 485 2-wire, Transceiver Impedance: ¼ unit load
Network Bias and Termination are NOT provided internally by the AVR Control Module
Full Master Node State Machine
Data Rates 9600, 19200, 38400, 76800 and 115200
MAC address is software configurable
CONFIGURATION USB 2.0, Isolated, Type C Connector, Optional Bluetooth (Ver 4.2 or later)
Connect to Computer running AccuValve Insight Software
DEVICE PORT RJ-45 Port, Connect to Accutrol Device ARS or ADS with Factory Supplied Cable only
STATUS INDICATORS LED Indicators for Power, Alarm, AO, BACnet, USB, AVR Status & Bluetooth
I/O TERMINAL BLOCKS 2 and 3 Position Removable Vertical Plugs, Wire Size Range 12-30 AWG
COMPLIANCE
RoHS