Page 54
SECTION 9 - MAINTENANCE
Scheduled maintenance for the AVR is not required; however, each AccuValve does include an
access cover which can be removed to inspect the airflow sensors if desired.
9.1 Round Valve Access Cover
CAUTION:
Wear eye protection, cut-resistant gloves, and clothing suitable for working
with sheet metal. Failure to do so may result in personal injury.
9.1.1 Loosen the 3/8” bolt enough to allow the access door to slide forward.
CAUTION:
If the bolt is removed from the captive nut, the access cover can spring open
possibly causing injury.
9.1.2 Using two hands; squeeze the access
cover and slide it forward over the valve
enough to uncover the access opening.
9.1.3 Once the cover is slid forward or
removed, the airflow sensors can be visually
inspected.
9.1.4 When inspection is complete, slide the
access cover over the opening, being careful
not to damage gasket in the process.
9.1.5 Verify the access cover is in position to
completely cover the opening. Secure cover in place by tightening the 3/8” bolt using care not
to over tighten.
Access Cover
Loosen
3/8” Bolt
Sensors