Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 22
6.5.3
AVR Insight Dashboard
The AVR Dashboard provides real-time information associated with AVR temperature
and airflow control system while also providing access to the field-configurable
parameters. During the startup process, the next step after the AVR6 APP Configuration
has been completed is to select the “AVR6000 Configuration Menu” located at upper
left corner of the dashboard which will provide access to the items that must be
configured before proceeding.
6.5.3.1
AVR6000 Configuration Menu
The AVR6000 Configuration Menu provides access to the items that are relevant to the
APP TYPE that has been configured. Each item in this menu must be configured correctly
during the field startup process otherwise the AVR will not function properly. Each item
in the AVR6000 Configuration Menu is described in the following paragraphs.
6.5.3.1.1
Setpoint Configuration
The AVR can be configured to provide up to 4 different setpoint modes which are used
to maximize energy savings and accommodate application-specific sequences. The
setpoint modes can be switched locally using the hardwired dry-contact inputs DI-1 and
DI-2 on the AVR6000 controller, or through BACnet using multi-state values MSV1
through MSV4. If the ARS2 includes the optional motion sensor, DI-1 cannot be used for
an external device because the ARS2 motion sensor is configured using the DI-1 input. A
few examples are provided on the following pages to help explain the Setpoint
Configuration process.
1 Setpoint Configuration
Note:
Before proceeding, verify all
control setpoints and operating modes are
clearly defined and all airflow control
setpoints are within the operating range of
the AccuValve(s).