Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 23
Example 1:
APP 1 (Supply Only), No Discharge Temp Control, One Setpoint Mode
Step 1:
Enter a description for Setpoint
Mode 1 using 10 characters max. This
description will appear on the ARS display
to indicate the active mode.
Step 2:
In the MODE 1 column, enter the
control setpoint values in the active cells.
Step 3:
Select “Update Controller” to save
changes.
Example 2:
APP 2 (Supply with GE/Return), with Discharge Temp Control and Two Setpoint
Modes. Occupancy Sensor is connected to DI-2
on the AVR6000 Controller
Step 1:
Enter a description for Setpoint
Modes 1 and 2 using 10 characters max
for each. This description will appear on
the ARS display to indicate the active
mode.
Step 2:
In the MODE 1 and 2 columns,
enter the control setpoint values in the
active cells.
Step 3:
Select “Update Controller” to save
changes.
Example 3:
APP 3 (Supply with GE/Return and Fume Hood), with Discharge Temp Control and
Three Setpoint Modes. Occupancy Sensor is connected to DI-2 on the AVR6000 Controller and
Decon Mode triggered through BACnet point MSV3.
Step 1:
Enter a description for Setpoint
Modes 1, 2, and 3 using 10 characters
max for each. This description will appear
on the ARS display to indicate the active
mode.
Step 2:
In the MODE 1, 2, and 3 columns,
enter the control setpoint values in active
cells.
Step 3:
Select “Update Controller” to save
changes, select “Cancel Change” to revise.