Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 37
6.5.3.2.2
Exhaust Indicators - Right Side of Dashboard
6.5.3.2.3
Room Indicators - Center of Dashboard
Room Offset Gauge
Shows the real-time differential between the supply airflow
and total exhaust airflow. The range of this gauge is
configured to show no offset (neutral) in the center,
negative offset to the left and positive offset to the right.
This gauge is shown for Apps 2 through 4.
Room Temperature and RH Indicator
Shows the current room temperature, RH, the active room
temperature setpoints with status icons, and the current
setpoint mode status.
Air Changes Per Hour (ACH)
Shows the current air change rate based on the room
conditions such as supply, exhaust, and room dimensions.
To Set the room dimensions for the air change rate
calculation; hover over the ACH Gauge and double click
when the appears.
Yellow Setpoints
These yellow box icons indicate that there is a minimum or maximum
setpoint associated with the range of the measurement for that given
mode of operation.
GE/Return Gauge
Shows the active
airflow measurement
and setpoint of the
AVT GE/Return airflow
control valve. The
gauge range shall be
configured to match
the full-scale range of
the AVT GE/Return
valve’s analog output.
This gauge is shown
for all Apps that
include a general
exhaust valve.
GE/Return Position Indicator
Shows the AVT general
exhaust/return valve position as
indicated by the AVR control
output signal. Select to override
control and indicator turns red.
This indicator is shown for Apps
that include a general exhaust
valve.
Total Room Exhaust Gauge
Shows the sum of all measured
exhaust airflows within the room.
The range of this gauge is based
on the GE/Return and the Fume
Hood(s).
Fume Hood Exhaust Gauge
Shows the active total fume hood exhaust
airflow. For App 4, AccuNet is used to sum
multiple fume hood exhaust values & provide
the totalized value to the AVR6000. The
gauge range shall be configured to match the
FS range of the AVC exhaust valve’s analog
output. This gauge is shown for Apps 3 and 4.