Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 47
6.5.3.6.11
Constant Airflow Configuration
Reference Section 6.6.5.4 for explanation of the Constant Airflow Volume
Configuration.
6.5.3.6.12
Filter Adjust
Adjustable averaging filters are provided for the airflow measurement signals if
necessary. The level of filtering can be set from Min to Max using the slider located
next to the parameter. Most applications will not require filtering, however there
are times when the filter function can be useful to stabilize measured values that are
noisy.
CAUTION:
Higher filter values will slow down measurement response which also
reduces the control speed of response. Always confirm the system control response
meets the requirements of the application when adjusting filter values.
6.5.3.6.13
Help / About AccuValve Insight
Help provides access to the