Installation & Operation Manual - Model AVR6000
Contents of this Manual are Subject to Change Without Notification
Page 21
6.5.2
AVR APP Configuration
After you establish communications with an AVR controller, the AVR APP Configuration
window will appear. If the APP has not yet been configured, it is mandatory to complete
the configuration by selecting the APP TYPE and APP OPTIONS as shown below. If the
AVR APP has previously been configured, verify the configuration is correct, and
continue to the dashboard by selecting the “Continue” button located on the lower left
of the window.
Note:
Prior to configuring the AVR APP, confirm installation and field configuration and
wiring of all devices matches the submittal drawings and design documentation.
For APPs 3 and 4, fume hood controllers shall be field configured independent of the AVR
configuration.
STEP 1:
Select the APP TYPE that matches the field configuration.
STEP 2:
Select the APP OPTIONS starting at the top and working your way down to the
last option. The “Update Controller” button will become active only after Steps 1 and 2
have been completed.
STEP 3:
Verify the graphic image matches the application as configured in Steps 1 and 2.
STEP 4
: If the graphic image matches the application, select “Update Controller”. If the
graphic image does not match the application, repeat the configuration process by
starting at Step 1.