![Acadia AH3024FP Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/acadia/ah3024fp/ah3024fp_manual_3582491040.webp)
40
1. Loosen the inlet (IN) pressure tap by turning screw
counterclockwise. See (A).
2. Attach manometer using a ¼ in (6 mm) I.D. hose. . Light pilot
and burner. Check pressure to ensure it is between the minimum
and maximum recommended pressure settings.
3. Turn off burner and pilot.
4. Disconnect hose and tighten the inlet (IN) pressure tap by
turning screw clockwise. Screw should be snug. Do not over
tighten.
5. Relight pilot and burner. Then reattach manometer to the
inlet pressure tap (A) to verify the tap is completely sealed.
Manometer should read no pressure.
Manifold Pressure Test
1. Light pilot.
2. Loosen manifold (OUT) pressure tap by turning screw counter-clockwise (see (B).
3. Attach manometer to pressure tap using a ¼ in (6 mm) I.D. hose.
3. Turn off remote and wait 2 seconds.
4. Turn on remote and wait 2 seconds.
5. Turn off remote.
This should clear the lockout mode. Turn on the remote and start the appliance. Ensure the master switch is in the “ON”
position. If the lockout mode is still on, follow these steps:
1. Turn off the remote.
2.
If you see the snowflake icon, press the Mode button and toggle it to IPI mode.
3. Shut off AC power to the ignition control module (shut off breaker).
4. Toggle master switch to off. Wait 30 seconds.
5. Turn on AC power by turning on breaker.
6. Turn on remote, then turn off remote.
7. Toggle master switch back on.
8. Press Mode button on remote. Select CPI mode to reignite the pilot. After pilot lights, turn on your remote to ignite.
After completing these steps, contact your authorized dealer if it won’t turn on.
HOMEOWNER OPERATION
ADJUSTMENT
Pressure Testing
The appliance and its main gas valve must be disconnected from the gas supply piping system during any pressure
testing of the system at test pressures in excess of ½ psi (3.5 kPa).
Make sure to apply these incoming pressure test with all other gas appliances on, or at full capacity in the house
for proper pressure reading.
Inlet Pressure Test
Pressure check taps for manifold (outgoing) and inlet (incoming) pressure have been incorporated
into the valve. The pressure tap marked OUT measures outgoing pressure. The pressure tap marked IN
measures incoming pressure.
If the inlet pressure reading is too high or too low, contact the gas company. Only a qualified gas service
technician should adjust incoming gas pressure.
IMPORTANT
IMPORTANT
A
B