165
Remote communication
Chapter 11
Verifying settings by secondary
injection
16
Remote communication
16.1
Binary signal transfer to remote end
Prepare the IED for verification of settings as outlined in
section 2
in this chapter.
There are two types of internal self-supervision of the RTC.
The I/O-circuit board is supervised as an I/O module. For example it generates ‘FAIL’ if the
board is not inserted. I/O-modules not configured are not supervised. When an RTC- module is
configured as a logical I/O module it is also supervised.
There is also communication supervision that generates the output ‘WARNING’ if one of the
RTC-modules signals ‘COMFAIL’. Each RTC-module has an error output (‘COMFAIL’)
which is set to a logical 1 if anything is wrong with the communication through the actual mod-
ule. Status for inputs and outputs as well as self-supervision status are available from the local
HMI.
Test correct functionality by simulating different kind of faults. Also check that sent and re-
ceived data is correctly transmitted and read.
A test connection is shown in
figure 36
. A binary input (BI) is connected to an RTC function
input at end1, for example SEND01, and at the other end a binary output (BO) is connected to
the received function output, for example REC01. The binary signal is transferred to the remote
end (end2) through a communication link. Check at the remote end that the corresponding signal
(REC01) has been received. Repeat the test for all the signals used by the RTC function.
Figure 36:
Test of RTC with I/O.
+
BI
BO
REx670
REx670 (End 1)
(End 2)
-
Communication
link
en05000001.vsd
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...