![ABB RELION REL670 Скачать руководство пользователя страница 86](http://html.mh-extra.com/html/abb/relion-rel670/relion-rel670_installation-and-commissioning-manual_4707086.webp)
78
Preparing for test
Chapter 11
Verifying settings by secondary
injection
Test\Function test modes\function category\function instance
2.
Browse to the function instance that should be released.
Use the left and right arrow buttons. Press ‘E’ when the desired function
has been found.
3.
Select ‘Yes’. Press 'E' and the new setting is valid.
2.7
Disturbance report
2.7.1
Introduction
The following functions are included in the disturbance report function:
•
Disturbance recorder
•
Event list
•
Event recorder
•
Fault locator (not included in all products)
•
Trip value recorder
•
Indications
If the disturbance report is running, then its sub-function are also running and so it is not possible
to only switch these functions off. The disturbance report function is switched off from PCM600
or from the local HMI.
2.7.2
Disturbance report settings
When the IED is in test mode, the disturbance report can be made active or inactive. If the dis-
turbance recorder is turned on during test mode, recordings will be made. When test mode is
switched off all recordings made during the test session are cleared.
Settings for the control of the disturbance recorder during test mode are located in the local HMI
under:
Settings\General settings\Monitoring\Disturbance report\DisturbanceRe-
port(RDRE)\
2.7.3
Disturbance recorder (DR)
Evaluation of the results from the disturbance recording function requires access to a PC either
permanently connected to the IED or temporarily connected to the Ethernet port (RJ 45) on the
front. The PCM600 software package must be installed in the PC.
Disturbance upload can be performed by the use of PCM600 or by any third party tool with IEC
61850 protocol. Reports can automatically be generated from the PCM600 tool. Disturbance
files can be analyzed by any tool reading Comtrade formatted disturbance files.
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...