136
Control
Chapter 11
Verifying settings by secondary
injection
Testing the voltage difference
Set the voltage difference at 15%
UBase
on the HMI, and the test should check that operation is
achieved when the voltage difference
UDiff
is lower than 15%
UBase
.
The settings used in the test shall be final settings. The test shall be adapted to site setting values
instead of values in the example below.
Test with no voltage difference between the inputs.
1.
Apply voltages U-line (e.g.) = 80% UBase and U-Bus = 80% UBase.
2.
Check that the AUTOENOK and MANENOK outputs are activated.
3.
The test can be repeated with different voltage values to verify that
the function operates within the set UDiff values. Check with both U1
and U2 respectively lower than the other.
Test with a voltage difference higher than the set UDiffSC
1.
Increase the U-bus to 110% UBase, and the U-line = 90% UBase and
also the opposite condition.
2.
Check that the two outputs for manual and auto synchronism are not
activated.
Testing the phase angle difference
The phase angle differences
PhaseDiffM
and
PhaseDiffA
respectively are set to their final set-
tings and the test should verify that operation is achieved when the phase angle difference is low-
er than this value both leading and lagging.
Test with no voltage difference
1.
Apply voltages U-line (e.g.) = 100% UBase and U-bus = 100% UBase,
with a phase difference equal to 0 degrees and a frequency differ-
ence lower than fSynchMax.
SYN1
U-line
UL1
Activate SYN1_FD1CLD
UL2
Activate SYN1_CB2CLD
U4
Activate SYN1_CB2CLD and CB3CLD
U-bus
U5
No activation of inputs necessary
SYN2
U-line
UL2
Activate SYN2_FD2CLD
U4
Activate SYN2_CB3CLD
U-bus
UL1
Activate SYN2_FD1CLD
U5
Activate SYN2_CB1CLD
SYN3
U-line
UL1
Activate SYN3_CB2CLD
UL2
Activate SYN3_FD2CLD
U5
Activate SYN3_CB1CLD and CB2CLD
U-bus
U4
No activation of inputs necessary
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...