19
Dimensions
Chapter 5
Installing the IED
Figure 7:
Panel-cut out dimensions for side-by-side flush mounting
Case size
Tolerance
A
±
1
B
±
1
C
±
1
D
±
1
E
±
1
F
±
1
G
±
1
6U x 1/2 of 19”
214.0
259.3
240.4
190.5
34.4
13.4
6.4 diam
6U x 3/4 of 19”
326.7
259.3
352.8
190.5
34.4
13.4
6.4 diam
6U x 1/1 of 19”
438.7
259.3
465.1
190.5
34.4
13.4
6.4 diam
xx05000505.vsd
B
A
C
G
D
E
F
Note!
With side-by-side flush mounting installation, only IP class 20 is obtained. To reach the IP class
54 the case-by-case flush mounting is recommended.