98
Distance protection
Chapter 11
Verifying settings by secondary
injection
Figure 31:
Operating principle and characteristic of the PSD function
The PSD can operate in two modes when configured for; “one of three phase operation” and
“two out of three phase operation”. Check the configuration to see which of these is valid for the
IED.
5.3.1
Testing overview
Procedure
1.
Re-configure the binary output from the ZOUT signal to the START
signal of the PSD function.
It is also possible to observe the START signal on the regular output ter-
minals, if provided during the engineering stage. Check the correspond-
ing IED documentation.
2.
Slowly decrease the measured voltages in all three phases until the
W-meter detects the appearance of the START signal.
3.
Increase the measured voltages to their rated values.
4.
Decrease instantaneously voltages in all three phases to the values,
which are approximately 20% lower than the set value R1IN.
The START signal must not appear.
jX
R
tP1
Impedance locus at power swing
99000159.vsd
−
⋅
KX X IN
1
−
X IN
1
X IN
1
KX X IN
⋅
1
−
⋅
KR R IN
1
KR R IN
⋅
1
−
R IN
1
IN
R
1
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...