135
Control
Chapter 11
Verifying settings by secondary
injection
Testing the frequency difference
The frequency difference is in the example set at 0.20 Hz on the local HMI, and the test should
verify that operation is achieved when the
FreqDiffSynch
frequency difference is lower than
0.20 Hz. The test procedure below will depend on the settings used.
Procedure
1.
Apply voltages U-line = 100% UBase, f-line=50.0 Hz and U-Bus =
100% UBase, f-bus = 50.2 Hz.
2.
Check that a closing pulse is submitted and at closing angle less
than 2 degrees from phase equality. Modern test sets will evaluate
this automatically.
3.
Repeat with U-Bus = 80% UBase, f-bus=50.25 Hz to verify that the
function does not operate when freqency difference is above limit.
4.
Repeat with different frequency differences e.g. 100 mH with f-bus
nominal and line leading and for example 20 mHz (or just above
fSynMin
) to verify that independent of frequency difference the clos-
ing pulse occurs within 2 degrees.
5.
Verify that the closing command is not issued when the frequency
difference is less than the set value fSynMin.
11.1.2
Testing the synchronism check
During test of the synchronism check function for a single bay arrangement, these voltage inputs
are used:
Voltage inputs
At test of the synchrocheck function for a 1
1
/
2
CB diameter the following alternative voltage in-
puts can be used for the three synchrocheck functions. The voltage is selected by activation of
different inputs in the voltage selection logic:
tBreaker
0.08 s
VTConnection
Line
tSyncM
0 s
tSyncA
0 s
FreqDiffBlock
Off
Parameter
Setting
U-line
UL1, UL2 or UL3 voltage input on the IED.
U-bus
U5 voltage input on the IED
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...