137
Control
Chapter 11
Verifying settings by secondary
injection
2.
Check that the AUTOOK and MANOK outputs are activated.
The test can be repeated with other
PhaseDiff
values to verify that the
function operates for values lower than the set ones. By changing the
phase angle on U1 connected to U-bus, between
±
d
ϕ
degrees. The user
can check that the two outputs are activated for a
PhaseDiff
lower than
the set value. It should not operate for other values. See
figure 34
.
Figure 34:
Test of phase difference.
3.
Change the phase angle bd
ϕ
and —d
ϕ
and verify that the
two outputs are activated for phase differences between these val-
ues but not for phase differences outside, see
figure 34
.
Testing the frequency difference
The frequency difference test should verify that operation is achieved when the
FreqDiff
fre-
quency difference is lower than the set value for manual and auto synchronism check respective-
ly and that operation is blocked when the frequency difference is bigger.
Test with FreqDiff = 0 mHz
1.
Apply voltages U-Line equal to 100% UBase and U-Bus equal to
100% UBase, with a frequency difference equal to 0 mHz and a phase
difference lower than the set value.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
Test with a frequency difference outside the set limits for manual and auto
synchrocheck respectively.
1.
Apply voltage to the U-line equal to 100% UBase with a frequency
equal to 50 Hz and voltage U-bus equal to 100% UBase, with a fre-
quency outside the set limit.
+d
ϕ
-d
ϕ
U-Bus
U-Line operation
U-Bus
No operation
en05000551.vsd
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...