![ABB RELION REL670 Скачать руководство пользователя страница 115](http://html.mh-extra.com/html/abb/relion-rel670/relion-rel670_installation-and-commissioning-manual_4707115.webp)
107
Current protection
Chapter 11
Verifying settings by secondary
injection
6.6
Thermal overload protection, one time constant (PTTR, 26)
Prepare the IED for verification of settings as outlined in
section 2
in this chapter.
Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical
signal TRIP, START and ALARM are equal to logical 0.
6.6.1
Measuring the operate and time limit of set values
Testing the protection without external temperature compensation (NonComp)
Procedure
1.
Quickly set the measured current (fault current) in one phase to
about 300% of IRef (to minimise the trip time), and switch the current
off.
2.
Reset the thermal memory under menu tree:
Reset\Reset temperature\ThermalOverload1TimeConst(PTTR,26)\THLn
3.
Switch the fault current on and take note of the temperature:
Test\Current protection\ThermOverLoad1TimeConst(PTTR,26)\THLn\TEMP
4.
Check the Alarm time limit AlarmTemp during injection.
Measure the signal ALARM until it appears on the corresponding binary
output or on the local HMI.
5.
Compare the measured temperature with the setting.
6.
Measure the THL protection trip time.
Use the TRIP signal from the configured binary output to stop the timer.
7.
Take the “TEMP” readings.
Compare with the setting of
TripTemp.
8.
Activate the BLOCK binary input.
The signals ALARM, START and TRIP should disappear.
9.
Reset the BLOCK binary input.
10. Check the reset limit (TdReset).
Measure the signal START until it disappears on the corresponding bina-
ry output or on the local HMI, take the “TEMP” readings and compare
with the setting of
ReclTemp
.
11. Compare the measured trip time with the setting according to the
formula.
12. Reset the thermal memory.
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...