80
Basic IED functions
Chapter 11
Verifying settings by secondary
injection
3
Basic IED functions
3.1
Parameter setting groups (ACGR)
Prepare the IED for verification of settings as outlined in
section 1 "Overview"
and
section 2
in this chapter.
3.1.1
Verifying the settings
Procedure
1.
Check the configuration of binary inputs that control the selection of
the active setting group.
2.
Browse the ‘ActiveGroup’ menu to achieve information about the ac-
tive setting group.
The ActiveGroup menu is located in the local HMI under:
Test\Function status\Setting groups
3.
Connect the appropriate dc voltage to the corresponding binary in-
put of the IED and observe the information presented on the HMI dis-
play.
The displayed information must always correspond to the activated input.
4.
Check that the corresponding output indicates the active group.
Operating procedures for the PC aided methods of changing the active
setting groups are described in the corresponding PCM documents and
instructions for the operators within the SCS are included in the SCS doc-
umentation.
3.1.2
Completing the test
Continue to test another function or end the test by changing the test mode setting to off.
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...