![ABB RELION REL670 Скачать руководство пользователя страница 159](http://html.mh-extra.com/html/abb/relion-rel670/relion-rel670_installation-and-commissioning-manual_4707159.webp)
151
Scheme communication
Chapter 11
Verifying settings by secondary
injection
12.2.2
Weak end infeed logic
WEI logic at permissive schemes
Procedure
1.
Check the blocking of the echo with the injection of a CR signal
>40 ms after a reverse fault is applied.
2.
Measure the duration of the echoed signal by applying a CR carrier
receive signal.
3.
Check the trip functions and the voltage level for trip by reducing a
phase voltage and applying a CR carrier receive signal.
Testing conditions
Only one type of fault is sufficient, with PSCH function. Apply three faults (one in each phase),
when ZC1P function is used. For phase L1-N fault, set these parameters:
Table 21:
Change all settings cyclically for other faults (L2-N and L3-N).
Weak end infeed set for trip
1.
Apply input signals according
table 21
.
2.
Activate the carrier receive (CR) signal of the terminal.
3.
After the relay has operated, turn off the input signals.
4.
Check that trip, carrier-send signal, and indication are obtained.
(note: a 200mS pulse)
Weak end infeed set for echo
1.
Apply input signals according
table 21
.
2.
Activate the carrier receive (CR) signal of the terminal.
3.
After the relay has operated turn off the input signals.
4.
Check that the carrier send signal is obtained.
12.2.3
Completing the test
Continue to test another function or end the test by changing the test mode setting to off.
Phase
I (Amps)
Phase-angle
(Deg)
V (Volts)
Phase-angle
(Deg)
L1
0
0
Set less than UPN<
0
L2
0
240
63
240
L3
0
120
63
120
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...