57
Fibre optic loop
Chapter 8
Establishing connection and
verifying the
SPA/IEC-communication
3
Fibre optic loop
The SPA communication is mainly used for SMS. It can include different numerical relays/ter-
minals with remote communication possibilities. The fibre optic loop can contain < 20-30 ter-
minals depending on requirements on response time. Connection to a personal computer (PC)
can be made directly (if the PC is located in the substation) or by telephone modem through a
telephone network with ITU (CCITT) characteristics.
Table 7:
Max distances between terminals/nodes
Figure 23:
Example of SPA communication structure for a station monitoring system
glass
< 1000 m according to optical budget
plastic
< 25 m (inside cubicle) according to optical budget
Where:
1
A separate minute pulse synchronization from station clock to obtain
±
1 ms accuracy for
time tagging within the substation might be required.
Local monitoring
system with
PCM600
IED670
IED670
IED670
Optical to electrical
converter, e.g. SPA-ZC 22
or Fiberdata modem
Teleph
one
modem
Teleph
one
modem
Remote monitoring
system with
PCM600
en05000672.vsd
Содержание RELION REL670
Страница 8: ...Contents ...
Страница 54: ...46 Checking the optical connections Chapter 6 Checking the external optical and electrical connections ...
Страница 72: ...64 About this chapter Chapter 9 Establishing connection and verifying the LON communication ...
Страница 78: ...70 Downloading settings and configuration from a PC Chapter 10 Configuring the IED and changing settings ...
Страница 174: ...166 Remote communication Chapter 11 Verifying settings by secondary injection ...
Страница 190: ...182 Maintenance Chapter 13 Fault tracing and repair ...
Страница 198: ...190 Glossary Chapter 14 Glossary ...